X-7
95-8470
Table X–1—UV/IR Detector Maximum Response Distances in Feet
Table X–2—Recommended Settings for JP-4, 5, 8 Fires
Sensitivity
Arc Rejection
30 inch Methane
1 Ft x 1 Ft Gasoline
1 Ft x 1 Ft Methanol
UV Standard
Low
40
30
15
Medium
60
45
20
High
80
65
35
Very High
100
100
55
UV Arc
Low
Medium
35
30
10
Rejection
Low
High
35
30
10
Medium
Medium
55
40
15
Medium
High
55
40
15
High
Medium
60
50
25
High
High
65
50
25
Very High
Medium
85
65
50
Very High
High
85
65
50
IR
Low
40
65
40
Medium
55
75
45
High
65
90
55
Very High
90
100
60
Typical response time less than 5 seconds.
NOTE:
Sensitivity level determines maximum response distance and is selected for UV and IR sensors individually (selected
through the configuration software). The maximum response distance for the UV/IR detector is the lesser of the two.
Fuel
Size
Distance
UV
IR
JP4
3 Ft x 3 Ft
150 Ft.
Very High
High
JP5
3 Ft x 3 Ft
150 Ft.
High
High
JP8
3 Ft x 3 Ft
150 Ft.
Very High
Medium
JP4
2 Ft x 2 Ft
100 Ft.
High
Medium
JP5
2 Ft x 2 Ft
100 Ft.
High
Medium
JP8
2 Ft x 2 Ft
100 Ft.
High
Medium
Typical response time less than 5 seconds.