B-1
95-8470
APPENDIX B
CANADIAN STANDARDS ASSOCIATION (CSA)
APPROVAL DESCRIPTION]
The Eagle Quantum Fire and Gas Detection/Suppression System (reference Figure B1) has the following CSA
approved configurations:
MODEL EQ2100LCU SERIES LOCAL CONTROL UNIT
(Up to four EQ2100LCU, four EQ2100CG and one EQ2100IM for maximum system.)
• Class I, Division 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA C22.2 #213.
• Operating Temperature Limits 0°C to +60°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Combustible Gas Performance verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152.
MODEL EQ2100LCUPS LOCAL CONTROL UNIT POWER SUPPLY AND
MODEL EQ2175PS, EQ2130PS AND EQ2110PS POWER SUPPLIES WITH MODEL EQ2100PSM SERIES
POWER SUPPLY MONITOR
• Ordinary Locations verified per CSA C22.2 #142.
• Operating Temperature Limits 0°C to +50°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
MODEL EQ2100LIOU LOCAL INPUT/OUTPUT UNIT
• Ordinary Locations verified per CSA C22.2 #142.
• Operating Temperature Limits 0°C to +50°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
Содержание Eagle Quantum 95-8470-05
Страница 116: ...Figure A1 A 10...
Страница 122: ...Figure B1 B 6...
Страница 125: ...APPENDIX D D 1 95 8470...
Страница 128: ...LON is a registered trademark of Echelon Corporation Modbus is a registered trademark of Modicon Inc...