B-4
MODEL EQ2200DCUEX SERIES DIGITAL COMMUNICATION UNIT
WITH MODEL CGS SERIES COMBUSTIBLE GAS SENSOR
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25
(For use with Sensor Separation Kit).
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA
C22.2 #213.
• Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per
CSA C22.2 #213 (For use with sensor separation kit.)
• EQ22EMDCUEX non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous
Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94 (For use with Sensor Separation Kit).
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Verified for 0 to 100% LFL methane-in-air atmospheres per CSA C22.2 #152. Accuracy: ±3% LFL from 0 to 50%
LFL, ±5% LFL from 51% to 100% LFL.
NOTE
The high temperature characteristic has NOT been CSA verified above 75°C.
SENSOR SEPARATION KITS
226365-106
Combustible, Aluminum, 3/4 inch NPT, 4 Position Connector
226365-113
Combustible, Aluminum, 3/4 inch NPT, Wiring Harness
226365-104
Toxic, Aluminum, 3/4 inch NPT
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
NOTE
Ensure sensor hazardous (classified) location rating is applicable for the intended use.
MODEL EQ2500ARM SERIES AGENT RELEASE MODULE
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
• EQ25EMARM non-incendive for Class I, Div. 2, Groups A, B, C and D; Temperature Code T4A Hazardous
Locations per CSA C22.2 #213.
• Enclosure Rating NEMA Type 4X per CSA C22.2 #94.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.