EQ2200DCU AND EQ2200DCUEX
DIGITAL COMMUNICATION UNIT
INPUT VOLTAGE—
24 vdc nominal, 18 to 30 vdc. 10% overvoltage will not
cause damage to the equipment.
POWER CONSUMPTION—
DCU with toxic gas sensor/transmitter:
95 ma maximum.
DCU with transmitter and combustible gas sensor:
180 ma maximum during normal operation, 500 ma
during startup.
INPUTS—
4 to 20 ma analog signal.
Non-intrusive calibration.
OUTPUTS—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating:
–40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
0 to 95% RH, non-condensing.
VIBRATION—
Meets MIL SPEC 810C, method 514.2, curve AW.
DIMENSIONS—
See Figure X-2.
EQ2500ARM AGENT RELEASE
MODULE
RELEASE OUTPUT RATING—
2 amperes at 30 vdc maximum.
SUPERVISORY CURRENT—
2.0 ma, ±1.0 ma each circuit.
INPUT VOLTAGE—
24 vdc nominal.
INPUT CURRENT—
Standby:
75 ma maximum at 24 vdc.
Alarm:
120 ma maximum at 24 vdc.
STATUS OUTPUTS—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating:
–40°F to +167°F (–40°C to +75°C).
Storage:
–67°F to +185°F (–55°C to +85°C).
HUMIDITY RANGE—
5 to 95% RH, non-condensing.
VIBRATION—
Meets MIL SPEC 810C, method 514.2, curve AW.
DIMENSIONS—
See Figure X-2.
X-9