VII-10
Module
Switch Position
Address
S3–2
S4–1
S4–2
1
ON
ON
ON
2
ON
ON
OFF
3
ON
OFF
ON
4
ON
OFF
OFF
5
OFF
ON
ON
6
OFF
ON
OFF
7
OFF
OFF
ON
8
OFF
OFF
OFF
T0017A
Table VII-4—Switch Positions for Release Module Addresses
S1
Single
Dual
Explosive
Solenoid
Solenoid
Initiators
SOL
X
X
—
SQB
X
—
X
Switch S1 Position Assignments
T0018A
OFF
Solenoids
ON
Explosive Initiator
Switch S3–1 Position Assignments
Table VII-5—Switch Positions for Solenoid/Explosive Initiator
1
12
S2
DS1
TB1
SOL
S1
SQB
RELEASE MODULE
W1
W2
MODULE ADDRESS ASSIGNMENT
RESET SWITCH
TROUBLE LED
ON
J1
1
2
1
2
}
A1864
S4
S3
Figure VII–11—Location of Switches and Jumpers on Release Module
Solenoids
Maximum Wire Length in Feet (Meters)
Manufacturer
Model
12 AWG
14 AWG
16 AWG
18 AWG
Skinner
LV2LBX25
800 (244)
500 (152)
310 (94)
200 (61)
ASCO
8210A107
520 (158)
325 (99)
200 (61)
130 (40)
ASCO
8210G207
825 (251)
520 (158)
325 (99)
205 (62)
Skinner
73218BN4UNLVNOC111C2
860 (262)
540 (165)
340 (104)
215 (66)
Skinner
73212BN4TNLVNOC322C2
400 (122)
250 (76)
160 (49)
100 (30)
Skinner
71395SN2ENJ1NOH111C2
860 (262)
540 (165)
340 (104)
215 (66)
T0041B
Device
Maximum Wire Length in Feet
12 AWG
14 AWG
16 AWG 18 AWG
890181*
150
100
60
899175*
150
100
60
895630-000*
150
100
60
897494*
190
120
75
486500-001*
1500
1000
600
400
31-199932-004*
150
100
60
Squib
190
120
75
2 Amp Load
190
120
75
T0028B
*Fenwal Solenoid
Table VII-2—Maximum Wiring Length for Release Applications
Table VII-3—Maximum Wiring Length for FM Approved Solenoids for Deluge and Pre-Action Applications