B-3
95-8470
MODEL EQ2200UVIR SERIES UV/IR FLAME DETECTOR
• Explosionproof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
• Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and G; Class III;
Temperature Code T4A Hazardous Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Optional Q9001G Swivel Mount.
MODEL EQ2200DCU SERIES DIGITAL COMMUNICATION UNITS
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25
(For use with Sensor Separation Kit).
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous Locations per CSA
C22.2 #213.
• Non-incendive for Class II, Div. 2, Groups F and G; Class III; Temperature Code T4A Hazardous Locations per
CSA C22.2 #213 (For use with sensor separation kit.)
• EQ22EMDCU non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code T4A Hazardous
Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94 (For use with Sensor Separation Kit).
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Combustible gas performance verified with any CSA Certified stand alone linear 4 to 20 mA device per CSA C22.2
#152. Accuracy ±3% LFL from 0 to 50% LFL, ±5% LFL from 51% to 100% LFL.