95-8470
VII-11
SIGNAL AUDIBLE MODULE
WIRING
The signal audible module can support NFPA style Y or
style Z field wiring. Refer to Figures VII-12 through VII-
15 and determine which of the wiring styles will be
used. EOL resistor value is 10K ohms.
NOTE
Polarity shown is for activated condition. Polarity
is reversed for monitoring condition.
To ensure adequate operating voltage for the signaling
device, the maximum wiring length from the power
source to the output device must not exceed the values
shown in Table VII-6. (This wire length includes both the
wiring from the power supply to the signal audible module
and the wiring from the module to the signaling device.)
JUMPERS/SWITCHES
Note that each wiring diagram is accompanied by its
corresponding jumper/switch setting table. This table
shows the correct positions for jumper plugs W1
through W8 and switches SW2-1 and SW3-2. For
jumper plugs W1 through W8, ON = jumper installed,
OFF = jumper removed.
When the auxiliary power input is used, jumpers W9 and
W10 must be cut. See Figure VII-16 for the locations of
jumpers and switches on the circuit board.
ADDRESS SWITCH SETTING
Each signal audible module must be assigned a unique
address (1 to 8). This is accomplished using switches
SW2-2, SW1-1 and SW1-2 on the signal audible module
circuit board. Refer to Table VII-7 to determine the
correct switch positions for the desired address.
10K EOL
10K EOL
AUXILIARY POWER
+
24VDC
RET
10K EOL
CIRCUIT 4
CIRCUIT 1
CIRCUIT 3
TB1
1
2
5
6
7
8
9
10
11
12
C1865
W1
OFF
W2
OFF
W1
OFF
W3
OFF
W4
ON
JUMPERS
W5
ON
W6
ON
W7
ON
W8
OFF
SW2–1
OFF
SW3–2
ON
SWITCHES
–
–
–
–
+
+
+
+
Figure VII–12—One Style “Z” and Two Style “Y” Circuits
for Signal Audible Module
10K EOL
10K EOL
AUXILIARY POWER
+
24VDC
RET
10K EOL
CIRCUIT 3
CIRCUIT 2
CIRCUIT 1
TB1
1
2
5
6
7
8
9
10
11
12
C1866
W1
OFF
W2
ON
W1
ON
W3
ON
W4
OFF
JUMPERS
W5
OFF
W6
OFF
W7
OFF
W8
ON
SW2–1
ON
SW3–2
OFF
SWITCHES
–
–
–
–
+
+
+
+
Figure VII–13—Two Style “Y” and One Style “Z” Circuits
for Signal Audible Module
AUXILIARY POWER
+
24VDC
RET
10K EOL
CIRCUIT 3
10K EOL
CIRCUIT 1
TB1
1
2
5
6
7
8
9
10
11
12
C1867
W1
OFF
W2
OFF
W1
OFF
W3
OFF
W4
ON
JUMPERS
W5
OFF
W6
OFF
W7
OFF
W8
ON
SW2–1
OFF
SW3–2
OFF
SWITCHES
–
–
–
–
+
+
+
+
Figure VII–14—Two Style “Z” Circuits for Signal Audible Module
10K EOL
10K EOL
AUXILIARY POWER
+
24VDC
RET
CIRCUIT 2
CIRCUIT 1
10K EOL
10K EOL
CIRCUIT 4
CIRCUIT 3
TB1
1
2
5
6
7
8
9
10
11
12
C1868
W1
OFF
W2
ON
W1
ON
W3
ON
W4
OFF
JUMPERS
W5
ON
W6
ON
W7
ON
W8
OFF
SW2–1
ON
SW3–2
ON
SWITCHES
–
–
–
–
+
+
+
+
Figure VII–15—Four Style “Y” Circuits for Signal Audible Module
Содержание Eagle Quantum 95-8470-05
Страница 116: ...Figure A1 A 10...
Страница 122: ...Figure B1 B 6...
Страница 125: ...APPENDIX D D 1 95 8470...
Страница 128: ...LON is a registered trademark of Echelon Corporation Modbus is a registered trademark of Modicon Inc...