background image

COM 1 -

Communication  network  connections:
Connect to COM 2 terminals of the next
device on the loop, A to A and B to B.

COM 2 -

Communication  network  connections:
Connect to COM 1 terminals of the
previous device on the loop, A to A and B
to B.

24 VDC -

Connect the "+" terminal to the positive
side of the 24 vdc power source. (Both "+"
terminals are connected internally.)

Connect the "-" terminal to the negative
side of the 24 vdc power source. (Both "-"
terminals are connected internally.)

4.

Connect the shields to the two designated "shield"
terminals. The two shield terminals are connected
internally to ensure shield continuity. 

Do not 

ground

either shield at the network extender enclosure.
Insulate the shields to prevent shorting to the
device housing or any other conductor.

5.

Check all field wiring to ensure that the proper
connections have been made.

6.

Inspect the enclosure O-ring to be sure that it is in
good condition and properly installed. Lubricate the
O-ring and the threads of the enclosure cover to
ease both installation and future removal of the
cover. The recommended lubricant is a silicone free
grease available from Detector Electronics. If the
installation uses catalytic type combustible gas
sensors, it is imperative that lubricants containing
silicone not be used, since they will cause
irreversible damage to the sensor. Place the cover
on the enclosure. Tighten only until snug. 

Do not

over tighten.

TYPICAL APPLICATIONS

Figure VII-45 shows a power supply monitor wired on a
LON between a UV detector and a DCU.

Figure VII-46 illustrates the power and communication
wiring for a UV detector, an IDC and a DCU, connected
to a standard LCU (EQ2100LCU) and an LIOU.

Figure VII-47 illustrates the power and communication
wiring for a UV detector, an IDC and a DCU, connected
to the optional LCU (EQ2101LCU) and an LIOU.

Figure VII-48 shows the power and communication
wiring for a UV/IR detector, an EQ2500SAM and an
EQ2500ARM, connected to a standard LCU
(EQ2100LCU) and an LIOU.

Figure VII-49 shows a network extender wired between
a UV detector and a DCU.

Figure VII-50 shows a high temperature UV detector
wired between a standard UV detector and a DCU.

95-8470

VII-31

Table VII-13—Maximum Wiring Length from Nominal 24 vdc 

Power Source to Network Extender

Wire Size

Maximum Wiring Distance

Feet

Meters

18 AWG (1.0 mm2)*

2200

650

16 AWG (1.5 mm2)*

3500

750

14 AWG (2.5 mm2)*

5600

1700

* Approximate Metric Equivalent.

Содержание Eagle Quantum 95-8470-05

Страница 1: ...8470 05 Eagle Quantum Fire and Gas Detection Releasing System Detector Electronics Corporation 6901 West 110th Street Minneapolis Minnesota 55438 USA Tel 952 941 5665 or 800 765 3473 Fax 952 829 8750...

Страница 2: ...Devices EQ2200IDC SERIES INITIATING DEVICE CIRCUIT IV 1 Description IV 1 EQ2200UV UV FLAME DETECTOR IV 1 Description IV 1 Software Selectable Options IV 2 EQ2200UVHT Hi Temp UV FLAME DETECTOR IV 4 De...

Страница 3: ...I 32 Section VIII Switch Setting GATEWAY VIII 1 LOGIC CONTROLLER VIII 3 ISOLATION MODULE VIII 3 LON SLC DEVICE ADDRESS SWITCH SETTING VIII 3 Section IX System Startup PRE COMMISSIONING CHECKLIST IX 1...

Страница 4: ...ing 3 To prevent unwanted actuation alarms and extinguishing devices must be secured prior to performing system tests Section I System Overview SYSTEM DESCRIPTION The Eagle Quantum System serves multi...

Страница 5: ...stallation requirements MAJOR COMPONENT DESCRIPTIONS The system consists of three basic components see Figure I 1 INTELLIGENT FIELD DEVICES ON LOCAL OPERATING NETWORK SIGNALING LINE CIRCUIT LON SLC Th...

Страница 6: ...ode it will annunciate a trouble condition If a Fire Alarm is detected by a Flame Detector or Initiating Device Circuit IDC the affected node will send a special Acknowledged Exception Report AER dire...

Страница 7: ...nication with the field devices even if there is a LON SLC short circuit directly adjacent to the LCU FIELD DEVICES WITHOUT POWER All Eagle Quantum field devices are designed so that a pass through ci...

Страница 8: ...of the LON SLC wiring by isolating shorts and monitoring for ground faults It also provides electrical isolation for the two serial communication ports between the gateway and host devices OPTIONAL L...

Страница 9: ...d bar graph will track the status of each address where activity is occurring by sequencing through each event by order of address DEVICE ADDRESS All three digits are on and the decimal point for each...

Страница 10: ...and Ground Fault F10 Fault F11 Low Voltage Fault F12 oi Fault F13 290 Volt Fault F20 Not Communicating Com 1 or Com 2 fault F60 Invalid Configuration or Unable to Configure cps Counts Per Second Displ...

Страница 11: ...tion of the gateway LON SLC diagnostics check for shorts and opens in the LON SLC wiring In the event of a problem the fault is annunciated in the gateway status word and the gateway fault relay is ac...

Страница 12: ...hbutton switches and nine LEDs See Figure II 2 KEY SWITCH The key switch on the front panel of the logic controller is used to select from four operating modes Normal Acknowledge Silence Enable Reset...

Страница 13: ...ching and must be cleared by resetting with the key switch Det Tronics configuration software should be used to determine the specific problem POWER FAULT Yellow Indicates that a power supply fault ha...

Страница 14: ...buzzer will again turn on NOTE If a trouble condition has been acknowledged and the condition exists for more than 24 hours the buzzer will again sound EQ2100IM ISOLATION MODULE FEATURES Ground fault...

Страница 15: ...k devices the power supply monitor utilizes a unique patented technique for detecting network wiring problems This feature minimizes the possibility of a communication breakdown in the event of a wiri...

Страница 16: ...when the Reset button is pressed or a fault occurs Pressing the Reset button resets the microprocessor on the card causing it to re initialize At this time the Trouble light on the LCU is also turned...

Страница 17: ...e sequence The agent release output circuit is rated for 24 vdc control devices Each release output can supervise and activate up to two solenoid control heads Tables III 1 and III 2 identify the devi...

Страница 18: ...amperes at 24 vdc enough to meet the power requirements of today s ADA UL 1971 signaling appliances The Signal Audible Module is located in the LIOU and is supervised by the LCU In the event of modul...

Страница 19: ...to the gateway at the rate determined at the time of configuration When programmed for response to a fire alarm condition a special Acknowledged Exception Report AER is immediately sent to the Logic...

Страница 20: ...arcs or electrostatic discharge while maintaining the ability to reliably detect the UV given off by a flame The arc rejection mode is not recommended unless these false alarm sources are present wit...

Страница 21: ...mode If the fire signal meets the programmed arc rejection requirements the time delay begins A fire output is generated if the fire signal continues for the duration of the time delay Standard mode A...

Страница 22: ...ned to provide reliable fire protection in applications where the use of either ultraviolet UV or infrared IR detectors alone can result in false alarms When used alone a UV detector can respond to so...

Страница 23: ...t types of logic that can be used for processing fire signals either standard or arc rejection ARC REJECTION MODE The arc rejection mode recommended enables the detector to prevent nuisance fire alarm...

Страница 24: ...oblem Repeat configuration UV fault Defect in UV module See extended status IR fault Defect in IR module See extended status Power up Detector in power up time delay Solution Wait for detector to exit...

Страница 25: ...fire output is generated if the fire signal continues for the duration of the time delay Automatic or Manual oi The EQ2200UVIR is equipped with the Optical Integrity oi feature The oi test is perform...

Страница 26: ...d whenever power is applied During normal operation only the green LED is illuminated The red LED is used to indicate a calibration power up fault or alarm condition The flashing rate of the red LED i...

Страница 27: ...Solenoids Initiators The releasing output devices listed in Table IV 6 are recommended for use with the Agent Release Module The solenoids listed in Table IV 7 are compatible with the Agent Release M...

Страница 28: ...d by setting switches on an eight position DIP switch valid address range is 5 to 250 Status LEDs Three LEDs located at the center of the circuit board provide a visual indication of device status con...

Страница 29: ...igning a system it is important to realize that increasing the number of nodes on the communication loop can result in an increase in the amount of time required for a status change message from a det...

Страница 30: ...let component of solar radiation UV radiation generated by periodic lightning or sparks in the area can be effectively ignored by the detector using the arc rejection feature or time delay UV detector...

Страница 31: ...however it should be noted that if these steady state infrared sources are hot enough to emit adequate amounts of infrared radiation in the response range of the IR sensor and if this radiation becom...

Страница 32: ...the designated hazardous area to reduce the likelihood of picking up radiation from distant sources See Figure 1 Detectors should be located in positions best suited for covering the area to be protec...

Страница 33: ...to a different or new environment calibration should be checked frequently to determine the proper interval between periodic calibrations Before performing calibration the operator should examine the...

Страница 34: ...herefore precautions should be taken to ensure that the combustible gas has been cleared before classifying the area as safe V 5 95 8470 ACTIVE ELEMENT REFERENCE ELEMENT THERMAL BARRIER FLAME ARRESTER...

Страница 35: ...clogged as a result of painting or house cleaning The routine maintenance procedure should include covering the sensor with a plastic bag when painting or cleaning The bag should be removed as soon a...

Страница 36: ...concentrations of combustible gases for extended periods of time can introduce stress to the sensing element and seriously affect its performance After exposure to a high concentration of combustible...

Страница 37: ...r to Table VI 1 to determine the minimum wire size needed to prevent excessive voltage drop from power supply to device for a given current load To use Table VI 1 first determine the total current loa...

Страница 38: ...iring length should not exceed 1600 feet 500 meters SHIELD GROUNDING Two shield ground terminals are provided inside the junction box of each field device and also at the LCU Connect the shield ends t...

Страница 39: ...d to prevent damage to electrical connections caused by condensation within the conduit ELECTROSTATIC DISCHARGE Many system electronic modules contain semiconductor devices that are susceptible to dam...

Страница 40: ...UV Detector X 0 120 UV IR Detector X 0 120 DCUEX X 0 160 DCU with H2S X 0 075 DCU with PointWatch X 0 320 ARM X 0 120 SAM X 0 120 Network Extender X 0 090 Power Supply X 0 300 Other X Total Solenoid...

Страница 41: ...083 Hours Sum of Standby and Alarm Amp Hours Multiply by 1 1 10 Safety Factor X Total Battery Amp Hour Requirement T0014A FM MINIMUM REQUIREMENT FOR EXTINGUISHING SYSTEMS IS 24 HOURS STANDBY TIME AND...

Страница 42: ...nized Test Laboratory NRTL labeled enclosure Refer to the Specifications section for mounting dimensions NOTE Power supplies require unrestricted air flow for proper cooling 2 Securely mount the cabin...

Страница 43: ...pply monitor See Figure VII 3 6 Connect the B terminal on the power supply monitor to the negative side of the backup battery Connect a correctly sized circuit breaker or disconnect switch in the batt...

Страница 44: ...5 8470 VII 3 1 4 C B AC BREAKER DC BREAKER H N G 24 VDC OUTPUT POWER SUPPLY MONITOR 12 11 10 9 8 7 6 5 4 3 2 1 POWER SUPPLY 12 VDC 12 VDC NRTL CABINET BATTERY CIRCUIT BREAKER POWER DIST CKT 1 POWER DI...

Страница 45: ...acts at 3D and 3E To insert the resistor lead into the terminal depress the orange lever Terminals 4 to 6 DC Power EQ2101LCU only Two separate 24 vdc power supplies with common ground are required Con...

Страница 46: ...he next device on the link All devices sharing a common RS 485 link must have a common system power return Terminals 10 to 12 Three unsupervised inputs to the Logic Controller These inputs are typical...

Страница 47: ...circuit terminals with separate shield connections The LON SLC is polarity sensitive due to ground fault monitoring A23 shield connection for COM 1 A24 B side of signaling circuit for COM 1 A25 A sid...

Страница 48: ...daisy chained wiring A terminals are connected to A terminals and B terminals to B terminals of the next device on the link RS 485 A Connect one terminal to A of the previous device on the link and th...

Страница 49: ...UBLE LED ON 1 2 1 2 A1862 1 TB1 12 Figure VII 9 Location of Switches on Relay Module Module Switch Position Address S1 2 S2 1 S2 2 1 ON ON ON 2 ON ON OFF 3 ON OFF ON 4 ON OFF OFF 5 OFF ON ON 6 OFF ON...

Страница 50: ...elease module in the LIOU must be assigned a unique address 1 to 8 This is accomplished using switches S3 2 S4 1 and S4 2 on the release module circuit board Refer to Table VII 4 to determine the corr...

Страница 51: ...ease Module Solenoids Maximum Wire Length in Feet Meters Manufacturer Model 12 AWG 14 AWG 16 AWG 18 AWG Skinner LV2LBX25 800 244 500 152 310 94 200 61 ASCO 8210A107 520 158 325 99 200 61 130 40 ASCO 8...

Страница 52: ...le must be assigned a unique address 1 to 8 This is accomplished using switches SW2 2 SW1 1 and SW1 2 on the signal audible module circuit board Refer to Table VII 7 to determine the correct switch po...

Страница 53: ...Position Address SW2 2 SW1 1 SW1 2 1 ON ON ON 2 ON ON OFF 3 ON OFF ON 4 ON OFF OFF 5 OFF ON ON 6 OFF ON OFF 7 OFF OFF ON 8 OFF OFF OFF T0019A Table VII 7 Switch Positions for Signal Audible Module Add...

Страница 54: ...dress Switch Setting in the Switch Setting section Section VIII of this manual for complete information regarding the switch setting procedure 5 Install the communication module inside the junction bo...

Страница 55: ...tion Active indicates a 24 VDC ground fault condition Circuit 2 Active indicates a loss of AC input power Open indicates a loss of battery power EQ2200IDCSC SERIES INITIATING DEVICE CIRCUIT SHORT CIRC...

Страница 56: ...feet one meter of the cable run to allow for aiming and alignment of the detector 3 Attach the detector to the swivel mounting bracket 4 Remove the rear housing from the bulkhead 5 Connect the wires t...

Страница 57: ...NSOR HOUSING BULKHEAD CONDUIT ENTRY oi RING O RING O RING A1840 A1841 STRAP COVER LOCKING ASSEMBLY BARREL LENS CAP CATCH SCREW CATCH BLIND HOLE SCREW COVER LOCKING CLAMP REAR HOUSING Figure VII 20 EQ2...

Страница 58: ...r wires to the appropriate points on the P3 terminal Connect the 24 vdc power wires and the communication network cable to the appropriate points on the P2 terminal See Figure VII 27 for terminal iden...

Страница 59: ...space around the swivel to facilitate aiming and wiring of the detector Armored flexible conduit should be used for the final 3 feet one meter of the cable run to allow for aiming and alignment of the...

Страница 60: ...ctor A Mount the detector and mounting bracket assembly on the wall or ceiling Observe the following guidelines The mounting surface should be free of excessive heat and vibration Allow adequate space...

Страница 61: ...DICATES AN ELECTRONIC MALFUNCTION Figure VII 30 UV IR Detector Junction Box with Cover Removed A1913 JUNCTION BOX oi TEST LAMP 2 O RING IR SENSOR HOUSING IR oi RING UV SENSOR MODULE O RING oi TEST LAM...

Страница 62: ...Figure VII 32 and ensure that the oi test lamps are located at the top or side of the sensor module when viewed from the front the opening in the oi ring is at the bottom This will ensure proper opera...

Страница 63: ...mmunication module Set the address for the device Refer to Device Address Switch Setting in the Switch Setting section of this manual for complete information regarding the switch setting procedure Ch...

Страница 64: ...efer to the PointWatch instruction manual form number 95 8440 for complete installation and application information Refer to Figure VII 36 when wiring a PointWatch IR gas detector and a DCU The wiring...

Страница 65: ...o be free of combustible gases or vapors The DCUEX uses the following 1 The terminal wiring board is mounted at the bottom of the junction box 2 The transmitter board is mounted above the terminal wir...

Страница 66: ...the device Refer to Device Address Switch Setting in the Switch Setting section of this manual for complete information regarding the switch setting procedure 95 8470 VII 25 1 2 3 4 5 6 7 8 9 10 SIG...

Страница 67: ...r board must be mounted separate from the sensor high temperature applications etc separate the sensor only leaving the transmitter PC board inside the DCUEX enclosure When using this installation opt...

Страница 68: ...2 and the initiator between terminals 3 and 4 as shown in Figure VII 40 CAUTION Do not intermix different types of initiators in the release circuit Terminals 5 to 10 LON SLC signaling circuit termina...

Страница 69: ...III For convenience in determining the correct positions for address switches refer to the table Address Switch Settings at the back of this manual VII 28 9 10 7 8 5 6 3 4 1 2 13 14 11 12 JP1 JP2 JP3...

Страница 70: ...cuit for COM 1 Terminals 11 to 14 24 vdc power input Connect the module power supply to terminals 12 and 13 If an auxiliary output supply is used for powering signaling devices it should be connected...

Страница 71: ...uminum enclosure 2 Remove the cover from the network extender enclosure 3 Connect the 24 vdc power lead wires and the communication network cable to the appropriate points on the terminal block See Fi...

Страница 72: ...e available from Detector Electronics If the installation uses catalytic type combustible gas sensors it is imperative that lubricants containing silicone not be used since they will cause irreversibl...

Страница 73: ...operational 7 External loads are properly connected and EOL resistors are installed 8 DIP switches are set correctly Record this information for future reference 9 Devices are properly installed in t...

Страница 74: ...3 10 9 8 7 4 6 5 B A SHIELD SHIELD B A B A SHIELD SHIELD B A SENSOR POWER 4 TO 20 MA IN POINTWATCH CALIBRATE COM 1 COM 2 24 VOLTS DC 24 VOLTS DC TO GAS DETECTOR POWER SUPPLY J3 J4 AUX POWER J5 A B J1...

Страница 75: ...1 2 3 10 9 8 7 4 6 5 1 2 3 4 COM 1 COM 2 B A 24 VDC 10 9 8 7 6 SHIELD 5 1 2 3 10 9 8 7 4 6 5 B A SHIELD SHIELD B A COM 1 COM 2 CIRCUIT 2 CIRCUIT 1 B A SHIELD SHIELD B A SENSOR POWER 4 TO 20 MA IN POIN...

Страница 76: ...SHIELD SHIELD B A SHIELD B A SHIELD B A COM 1 COM 2 OUTPUT 2 OUTPUT 1 B A SHIELD SHIELD B A COM 1 COM 2 24 VOLTS DC J3 J4 AUX POWER J5 A B J1 J2 RS 485 MAIN AUX EQ2100LCU EQ2200UVIR EQ2500ARM EQ2100L...

Страница 77: ...LD 5 1 2 3 10 9 8 7 4 6 5 SHIELD A B SHIELD SHIELD A B SHIELD B A SHIELD SHIELD B A SENSOR POWER 4 TO 20 MA IN POINTWATCH CALIBRATE COM 1 COM 2 COM 1 24 VDC COM 2 24 VOLTS DC TO GAS DETECTOR POWER SUP...

Страница 78: ...B1990 3 4 5 6 1 2 10 11 12 7 8 1 2 3 4 COM 1 COM 2 B A 24 VDC 10 9 8 7 6 SHIELD 5 1 2 3 10 9 8 7 4 6 5 SHIELD A B SHIELD SHIELD A B SHIELD B A SHIELD SHIELD B A SENSOR POWER 4 TO 20 MA IN POINTWATCH...

Страница 79: ...parity Closed parity enabled 5 Parity type Open odd Closed even 6 Stop bits Open 1 stop bit Closed 2 stop bits PARITY ENABLE OFF NO PARITY ON PARITY ENABLED BAUD RATE BIT 2 MSB BAUD RATE BIT 1 BAUD R...

Страница 80: ...1 is recommended 3 Port 1 operation Open Modbus RTU Slave Closed Allen Bradley DF1 Slave 4 Port 2 operation Open Modbus RTU Slave Closed Modbus RTU Master to PLC 5 Select configuration port Open Port...

Страница 81: ...ill report on that address The status word will show the latest update which could be from any of the reporting modules at that address NOTE Logic controllers utilize two consecutive LON SLC addresses...

Страница 82: ...he EPROM after any change is made Changes to the logic controller also require downloading via the key switch Chassis ground stud must be connected to earth ground Check RS 485 connections and polarit...

Страница 83: ...tween regularly scheduled recalibrations can vary from one installation to the next In general the more frequently a system is checked the greater the reliability IMPORTANT 4 to 20 ma devices not manu...

Страница 84: ...d 1 Open the junction box cover and press the sensor replacement switch 2 The calibrate LED on the communication module flashes at a 1 Hz rate indicating it is ready for the zero input 3 Replace the s...

Страница 85: ...ues The red LED will blink at a 4 Hz rate The calibration will be logged as aborted Sensor Replacement Combustible Gas NOTE When replacing a sensor compare part numbers to be sure that the correct rep...

Страница 86: ...o zero due to removing the sensor In addition the calibration will not be aborted if the calibration procedure is not completed within 12 minutes 3 Replace the sensor 4 Wait at least 5 minutes for the...

Страница 87: ...H POINTWATCH Routine Calibration 1 Apply the zero gas 2 Activate the reed switch for at least 4 seconds The red LED blinks at a 2 Hz rate for 3 seconds while the reed switch is activated 3 The calibra...

Страница 88: ...If the detector responds indicating a fire when no fire has occurred check the area to see if UV sources are present If possible remove the sources or reposition the detectors so that the sources fal...

Страница 89: ...sensor and also check the oi ring opening for proper orientation If the fault does not clear or fault reoccurs a faulty sensor or electrical problem is indicated First replace the UV sensor module If...

Страница 90: ...either a Modbus RTU slave or an Allen Bradley DF1 slave Port 2 can be either a Modbus RTU slave or master Two 78 5 kb LON SLC ports provide the start and end of the communication loop for the detectio...

Страница 91: ...0 60 50 40 30 20 10 RELAY 2 RELAY 3 RELAY 4 FAULT RESET EAGLE QUANTUM GATEWAY DET TRONICS LON INSOLATOR EAGLE QUANTUM LON ISOLATOR GROUND FAULT GROUND FAULT POWER POWER COM 2 COM 1 DET TRONICS SLOT 1...

Страница 92: ...Q2200UV Operating 40 F to 167 F 40 C to 75 C Storage 67 F to 185 F 55 C to 85 C EQ2200UVHT Electronic Module 40 F to 167 F 40 C to 75 C UV Detector 40 F to 257 F 40 C to 125 C Storage 67 F to 185 F 55...

Страница 93: ...and Figure X 6 electronic module 5 25 13 3 2 5 6 4 MOUNTING BASE 1 2 INCH NUT USED TO ADJUST ELBOW TO DESIRED ANGLE 1 3 8 INCH NUT USED TO ROTATE SWIVEL DETECTOR ASSEMBLY TO DESIRED POSITION 3 4 INCH...

Страница 94: ...8 6 A1844 CONDUIT CABLE ENTRY 2 Figure X 4B Dimensions of EQ2200UV Detector in Inches Millimeters 0 32 0 81 OVAL SLOT MOUNTING TYPICAL FOUR PLACES 3 39 8 6 4 66 11 8 5 20 13 21 0 28 0 71 2 69 6 83 A18...

Страница 95: ...is utilized While this setting is required to reliably detect certain types of fires care must be taken to minimize the possibility of false alarms RESPONSE TIME Selectable for a 0 to 7 second time de...

Страница 96: ...Very High High 85 65 50 IR Low 40 65 40 Medium 55 75 45 High 65 90 55 Very High 90 100 60 Typical response time less than 5 seconds NOTE Sensitivity level determines maximum response distance and is s...

Страница 97: ...TO SECURE DETECTOR BRACKET TO SWIVEL MOUNT JUNCTION BOX MOUNTING BRACKET ATTACHES WITH TWO ENCLOSED FLATHEAD SCREWS 2 1 2 64 MM DIA 0 25 6 4 MM DIA 3 120 2 2 2 00 50 8 MM DIA B1303 B1303 Figure X 9 Q...

Страница 98: ...40 C to 75 C Storage 67 F to 185 F 55 C to 85 C HUMIDITY RANGE 0 to 95 RH non condensing VIBRATION Meets MIL SPEC 810C method 514 2 curve AW DIMENSIONS See Figure X 2 EQ2500ARM AGENT RELEASE MODULE RE...

Страница 99: ...ting 40 F to 167 F 40 C to 75 C Storage 67 F to 185 F 55 C to 85 C HUMIDITY RANGE 5 to 95 RH non condensing VIBRATION Meets MIL SPEC 810C method 514 2 curve AW DIMENSIONS See Figure X 2 EQ2400NE NETWO...

Страница 100: ...6 amps at 120 208 240 VAC EQ2175PS 24 15 12 amps at 120 208 240 VAC Specify 50 Hz or 60 Hz OUTPUT CURRENT EQ2110PS 10 amperes at 24 VDC EQ2130PS 30 amperes at 24 VDC EQ2175PS 75 amperes at 24 VDC POW...

Страница 101: ...OUTPUTS PER SYSTEM 32 maximum LIOU RELEASE MODULE RELEASE OUTPUT RATING 2 amperes at 24 vdc SUPERVISORY CURRENT 2 5 ma each circuit SIGNAL OUTPUT RATING 2 amperes at 24 vdc MODULES PER SYSTEM 8 maxim...

Страница 102: ...MICAL SENSORS Refer to the Electrochemical Gas Sensor Specification Data sheet form 90 1079 for specifications Electrochemical sensors available from Det Tronics include Hydrogen Sulfide Oxygen Carbon...

Страница 103: ...ype combustible gas sensors FLAME DETECTOR MAINTENANCE The flame detector requires no periodic calibration However to maintain maximum sensitivity the viewing window must be kept clean at all times To...

Страница 104: ...external or faceplate reset switch is held closed Gateway Fault LED is on and F50 or F51 is displayed A fault was detected on one of the LON communication boards Replace the gateway Gateway Fault LED...

Страница 105: ...1 xxx EQ22XXUVIR UV IR Flame Detector 006607 xxx EQ22XXDCU Digital Communication Unit specify gas 006733 xxx EQ25XXARM Agent Release Module 006738 xxx EQ25XXSAM Signal Audible Module 006941 xxx EQ24XX...

Страница 106: ...Air Shield Assembly 004483 001 W8066 UV Test Lamp 004404 005 Swivel Mount 003240 202 Sensor Module 006598 001 Electronic Module 002507 001 Window cleaner kit 002519 001 oi Ring 107427 040 O Ring larg...

Страница 107: ...erified per ANSI NFPA 72 1996 Combustible Gas Performance verified for 0 to 100 LFL methane in air atmospheres per FM 6320 H2S Toxic Gas Performance verified 0 to 20 50 or 100 ppm per FMRC requirement...

Страница 108: ...I Division 1 Groups B C and D Hazardous Classified Locations per FM 3615 Dust ignition proof for Class II Division 1 Groups E F and G Class III Hazardous Classified Locations per FM 3615 Non incendive...

Страница 109: ...atic Fire Alarm Signaling Performance verified per FM 3260 A Model EQ2200UV with B2 Module was verified to comply with the following performance criteria Response Characteristics SENSITIVITY FUEL SIZE...

Страница 110: ...ive for Class I Division 2 Groups A B C and D Class II Division 2 Groups F and G Class III Temperature Code T4A Hazardous Classified Locations per FM 3611 Enclosure Rating NEMA Type 4X per ANSI NEMA 2...

Страница 111: ...nch 40 Ft Low Standard Low Methane 30 inch 40 Ft Medium Arc Rej Low Propane 30 inch 30 Ft Medium Standard Medium Propane 30 inch 30 Ft Medium Arc Rej Medium Methanol 1 Sq Ft 40 Ft High Standard Low Me...

Страница 112: ...de T4A Hazardous Classified Locations per FM 3611 Non incendive for Class II Div 2 Groups F and G Class III Temperature Code T4A Hazardous Classified Locations per FM 3611 For use with sensor separati...

Страница 113: ...ode T4A Hazardous Classified Locations per FM 3611 For use with sensor separation kit EQ22EMDCUEX non incendive for Class I Div 2 Groups A B C and D Temperature Code T4A Hazardous Classified Locations...

Страница 114: ...use with the following automatic deluge and pre action solenoids Manufacturer Model Skinner LV2LBX25 ASCO 8210A107 ASCO 8210G207 Skinner 73218BN4UNLVNOC111C2 Skinner 73212BN4TNLVNOC322C2 Skinner 71395...

Страница 115: ...umidity Range 5 to 95 RH National Fire Alarm Code Performance verified per ANSI NFPA 72 1996 and gas performance verified per FM 6310 6320 OPTIONS An optional EQ2101LCU with EQ2101MR Mounting Rack is...

Страница 116: ...Figure A1 A 10...

Страница 117: ...Limits 55 C to 85 C Relative Humidity Range 5 to 95 RH Combustible Gas Performance verified for 0 to 100 LFL methane in air atmospheres per CSA C22 2 152 MODEL EQ2100LCUPS LOCAL CONTROL UNIT POWER SU...

Страница 118: ...Groups B C and D Hazardous Locations per CSA C22 2 30 Dust ignitionproof for Class II Division 1 Groups E F and G Class III Hazardous Locations per CSA C22 2 25 Non incendive for Class I Div 2 Groups...

Страница 119: ...s Locations per CSA C22 2 30 Dust ignition proof for Class II Division 1 Groups E F and G Class III Hazardous Locations per CSA C22 2 25 For use with Sensor Separation Kit Non incendive for Class I Di...

Страница 120: ...Accuracy 3 LFL from 0 to 50 LFL 5 LFL from 51 to 100 LFL NOTE The high temperature characteristic has NOT been CSA verified above 75 C SENSOR SEPARATION KITS 226365 106 Combustible Aluminum 3 4 inch N...

Страница 121: ...C22 2 30 Dust ignition proof for Class II Div 1 Groups E F G Class III Hazardous Locations per CSA C22 2 25 Non incendive for Class I Div 2 Groups A B C and D Class II Div 2 Groups F and G Class III...

Страница 122: ...Figure B1 B 6...

Страница 123: ...solated when a flammable atmosphere is present Cable glands or the conduit entries to be used with this apparatus shall be EEx d approved by a notified body relevant to the threads found with the encl...

Страница 124: ...manner as to protect the lens from mechanical damage UV IR FLAME DETECTOR Standard Temperature Version EEx d IIB H2 T6 Tamb 40 C to 75 C EEx d IIB H2 T5 Tamb 40 C to 90 C IP66 Extended Temperature Ver...

Страница 125: ...APPENDIX D D 1 95 8470...

Страница 126: ...O O O X O 68 O O X O O O X O 69 X O X O O O X O 70 O X X O O O X O Node Rocker Switch Address 1 2 3 4 5 6 7 8 71 X X X O O O X O 72 O O O X O O X O 73 X O O X O O X O 74 O X O X O O X O 75 X X O X O O...

Страница 127: ...X X O X 192 O O O O O O X X 193 X O O O O O X X 194 O X O O O O X X 195 X X O O O O X X 196 O O X O O O X X 197 X O X O O O X X 198 O X X O O O X X 199 X X X O O O X X 200 O O O X O O X X 201 X O O X...

Страница 128: ...LON is a registered trademark of Echelon Corporation Modbus is a registered trademark of Modicon Inc...

Отзывы: