DIAGNOSTIC MESSAGES - TROUBLESHOOTING GUIDE
PROGRAMMER DESCRIPTION
For replacement of UVM, TFM and M-II type controls, refer to the cross-reference provided at the end of
this section.
MEP100 SERIES
MEP100 and MEP101
These programmers provide relight operation, in the event of a flame failure, pilot trial for ignition is
reinitiated. The MEP101 will not lock out if flame signal is present during the Idle or Off cycle. With
flame signal present, lockout will occur 60 seconds after the start of a cycle and the air flow switch is
closed.
Pilot Ignited Burners
Refer to typical wiring arrangement beginning on page 38.
Normal Operation
With power applied and the limit operating control circuit (1-7) closed, the Operating Control LED
illuminates, the burner motor circuit is energized (Terminal 8).
After the air flow proving switch (7-6) closes, the interlock (air flow) LED is illuminated and a short
time delay period (3-5 seconds) begins.
At the expiration of the safe start check period, a 10 second pilot trial for ignition (PTFI) period is
initiated, illuminating the PTFI Led. Power is applied to Terminal 3, energizing the pilot gas valve
and to Terminal 4, energizing the spark ignition.
At the detection of pilot flame, the FLAME LED is illuminated, and the programmer holds that posi-
tion for 3 seconds to allow the to pilot stabilize.
Power is then applied to Terminal 5 energizing the main fuel valve and removing power from Termi-
nal 4, turning off the spark igniter.
When the operating control opens, the control de-energizes Terminal 3 and Terminal 5 and the pro-
grammer reverts back to an Idle state.
POSSIBLE CAUSE
SOLUTION
Check Programmer
Voltage on Terminal 5 at improper time.
Inspect wiring to main fuel valve
Welded watchdog relay
Replace MEC chassis
Internal diagnostic failure
Replace MEP programmer
Check Chassis
Voltage on Terminal 3 or 4 at improper time.
Inspect wiring to pilot valve and igniter.
Welded watchdog relay
Replace MEC chassis
Chassis Opto
Opto-Coupler(s) short circuited
Replace MEC chassis
Amplifier High Count Fail
Amplifier signal level high
Replace Amplifier module
Amplifier Auto Check Fail
Flame signal too high
Use orifice in sight pipe
Internal Amplifier diagnostic fault
Replace Amplifier module
Check Scanner
Defective shutter
Inspect scanner wiring, replace scanner
UV tube false firing
Replace UV tube or scanner
Check Blown Fuse
No power detected on terminal 3
Inspect defective pilot valve or igniter
Defective fuse
Replace fuse
Line Frequency Noise Detected
Spikes detected on AC mains
Check for SCR motors or DC drives
Inspect ground system
Fuel Value State Change
Terminal 5 (main fuel) detected on during PTFI
Check external wiring or replace MEC chassis
Check Amplifier
Amplifier not passing diagnostic tests
Replace Amplifier module
System Error
Noise transient
Check high energy ignition noise location. Be
sure it is not arcing to chassis or wrapped
with scanner wiring.
Содержание MOISTURE Link G2 DP
Страница 1: ...Operation Manual 2019 MODELS MSF DP DPSL DPXSL DPX4T DPX8T DPX12T DPX16GT Grain Dryer Controls...
Страница 2: ......
Страница 4: ...2...
Страница 7: ...GENERAL INSTRUCTIONS 3 5...
Страница 153: ...151...
Страница 154: ...152...
Страница 166: ...164...
Страница 190: ...188...
Страница 200: ...198...
Страница 201: ...199...
Страница 202: ...200...
Страница 203: ...201...
Страница 204: ...202...
Страница 205: ...203...
Страница 206: ...204...
Страница 207: ...205...
Страница 208: ...206...
Страница 209: ...207...
Страница 210: ...208...
Страница 211: ...209...
Страница 212: ...210...
Страница 213: ...211...
Страница 214: ...212...
Страница 215: ...213...
Страница 216: ...214...
Страница 217: ...215...
Страница 218: ...216...
Страница 219: ...217...
Страница 220: ...218...
Страница 221: ...219...
Страница 222: ...220...
Страница 223: ...221...
Страница 224: ...222...
Страница 225: ...223...
Страница 226: ...224...
Страница 227: ...225...
Страница 228: ...226...
Страница 229: ...227...
Страница 242: ...240...
Страница 243: ...241...
Страница 244: ...242...
Страница 245: ...243...
Страница 301: ...56 FIGURE 19 Red jumper wire Red wire...
Страница 302: ...57...
Страница 310: ...2011 Service Manual Rev A 282...
Страница 311: ...2011 Service Manual Rev A 283...
Страница 312: ...2011 Service Manual Rev A 284...
Страница 313: ...2011 Service Manual Rev A 285...
Страница 314: ...2011 Service Manual Rev A 286...
Страница 315: ...2011 Service Manual Rev A 287...
Страница 316: ...2011 Service Manual Rev A 288...
Страница 317: ...2011 Service Manual Rev A 289...
Страница 318: ...2011 Service Manual Rev A 290...
Страница 319: ...2011 Service Manual Rev A 291...
Страница 320: ...2011 Service Manual Rev A 292...
Страница 321: ...2011 Service Manual Rev A 293...
Страница 322: ...2011 Service Manual Rev A 294...