Geo Brick Drive User Manual
Drive Structure and Troubleshooting
276
Reloading PMAC firmware
The following steps ensure proper firmware reload/upgrade.
Step1:
Power up the unit while holding the BOOT SW switch down.
Step2:
Release the BOOT SW switch approximately 2-3 seconds after power-up.
Step3:
Launch the Pewin32Pro2.
Run the PMAC Devices window under Setup > Force All Windows To Device Number.
Click Test for the corresponding communication method.
Click ok for message “The PMAC is in Boostrap Mode”