Geo Brick Drive User Manual
Motor Setup
200
I2T Protection: Ixx57, Ixx58, Ixx69
The lower values (tighter specifications) of the Continuous/Instantaneous current ratings between the Geo
Brick Drive and motor are chosen to setup I2T protection.
If the peak current limit chosen is that of the Geo Brick Drive (possible values 10, 16, or 30 Amps) then
the time allowed at peak current is set to 2 seconds.
If the peak current limit chosen is that of the Motor, check the motor specifications for time allowed at
peak current.
Examples:
For setting up I2T on a 5/10-Amp Geo Brick Drive driving a 3/9-Amp motor, 3 amps continuous
and 9 amps instantaneous will be used as current limits. And time allowed at peak is that of the
motor.
For setting up I2T on a 5/10-Amp Geo Brick Drive driving an 8/16-Amp motor, 5 amps
continuous and 10 amps instantaneous will be used as current limits. And time allowed at peak is
2 seconds.
For setting up I2T on a 15/30-Amp channel on a Geo Brick Drive driving a 12/45-Amp motor, 12
amps continuous and 30 amps instantaneous will be used as current limits. And Time allowed at
peak is 2 seconds.
A 4-axis 8/16 Amp Geo Brick Drive, is driving a 7/20 Amp AC Induction Motor on channel 4.
The continuous current limit is 7. The instantaneous current limit is 16.
I15=0
; Trig Operations in Degrees
;#define ServoClk
P7003 ; ServoClk is defined in clock calculation section [KHz]
#define Mtr4ContCurrent
7
; Motor #4 Continuous Current Limit [Amps]
-User Input
#define Mtr4PeakCurrent
16
; Motor #4 Instantaneous Current Limit [Amps]
-User Input
#define I2TOnTime
2
; Time allowed at peak Current [sec]
-User Input
I457=INT(32767*(Mtr4ContCurrent*1.414/Ch4MaxADC)*cos(30))
I469=INT(32767*(Mtr4PeakCurrent*1.414/Ch4MaxADC)*cos(30))
I458=INT((I469*I469-I457*I457+I477*I477)*ServoClk*1000*I2TOnTime/(32767*32767))
Note
This (software) I2T protection is computed by PMAC to protect the
motor (results are estimated RMS values).
The Geo Brick Drive has its own built-in hardware I2T as an
additional layer of safety and drive protection.
Note
I2T has to be corrected to reflect the finalized magnetization current
Ixx77. This is done at a subsequent step in the AC Induction Motor
Setup.