DataKinetics DSC110 / DSC210 User Manual Issue 12
Page 77
7.13.7 Alarm Test Initiate
ALTEI
Alarm Test Initiate
Generates an active test alarm of the specified class, which will be entered in the
alarm log.
Syntax
ALTEI:{[CLA=2][CLA=3]};
Attributes None
Prerequisites
Only one test alarm may be active at any one time. Test alarms may only be
generated for classes 2 and 3.
Example ALTEI:CLA=3;
7.13.8 Alarm Test End
ALTEE
Alarm Test End
Clears a test alarm.
Syntax
ALTEE;
Attributes None
Prerequisites
The alarm test must already have been initiated.
Example ALTEE;