SiBE37-701
Troubleshooting by Remote Controller
Troubleshooting
247
Outdoor Unit
LA
l
l
l
Malfunction of power unit
—
LC
l
l
l
Malfunction of transmission between inverter and
control PC board
P1
l
l
l
Inverter over-ripple protection
P4
l
l
l
Malfunction of inverter radiating fin temperature
rise sensor
PJ
l
l
l
Faulty field setting after replacing main PC board or
faulty combination of PC board
System
U0
k
h
l
Gas shortage alert
U1
l
l
l
Reverse phase, open phase
U2
l
l
l
Power supply insufficient or instantaneous failure
U3
l
l
l
Check operation not executed
U3
k
h
l
Check operation is not completed.
U4
l
l
l
Malfunction of transmission between indoor and
outdoor units
U5
l
l
l
Malfunction of transmission between indoor units
U5
h
k
h
Malfunction of transmission between remote
controller and indoor unit
U7
l
l
l
Transmission failure (Across outdoor unit)
U8
l
l
h
Malfunction of transmission between main and sub
remote controllers
U9
l
l
l
Malfunction of transmission between indoor and
outdoor units in the same system
UA
l
l
l
Improper combination of indoor and outdoor units,
indoor units and remote controller
UC
k
k
k
Address duplication of centralized controller
UE
l
l
l
Malfunction of transmission between centralized
controller and indoor unit
UF
l
l
l
System is not set yet
UH
l
l
l
Malfunction of system, refrigerant system address
undefined
Central
Remote
Controller
and
Schedule
Timer
M1
k
or
h
l
l
PC board defect
M8
k
or
h
l
l
Malfunction of transmission between optional
controllers for centralized control
MA
k
or
h
l
l
Improper combination of optional controllers for
centralized control
MC
k
or
h
l
l
Address duplication, improper setting
Heat
Reclaim
Ventilation
64
k
h
l
Indoor unit’s air thermistor error
—
65
k
h
l
Outside air thermistor error
—
6A
k
h
l
Damper system alarm
—
6A
l
l
l
Damper thermistor error
—
6F
k
h
l
Malfunction of simple remote controller
—
6H
k
h
l
Malfunction of door switch or connector
—
94
l
l
l
Internal transmission error
—
k
: ON
h
: OFF
l
: Blink
Malfunction
code
Operation
lamp
Inspection
display
Unit No.
Malfunction contents
Page
Referred
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Содержание VRV III REYQ10PY1B
Страница 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Страница 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Страница 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Страница 395: ...Piping Diagrams SiBE37 701 384 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12P 3D058154B S1NPH S2NPL ...
Страница 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Страница 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Страница 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Страница 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Страница 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Страница 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Страница 414: ...SiBE37 701 Wiring Diagrams for Reference Appendix 403 2 3 Indoor Unit FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125PVEB ...
Страница 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Страница 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Страница 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Страница 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Страница 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Страница 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Страница 447: ...Example of connection SiBE37 701 436 Appendix ...
Страница 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Страница 467: ...SiBE37 701 iv Index ...
Страница 471: ...SiBE37 701 viii Drawings Flow Charts ...