SiBE37-701
Test Operation
Test Operation
179
[How to check how many units are connected]
It is possible to find out how many indoor units are active and connected by operating the push-
button switch on the printed circuit board (A1P) of the working outdoor unit.
Make sure that all the indoor units connected to the outdoor unit are active.
Follow the 5-step procedure as explained below.
The LEDs on the A1P shows the operating status of the outdoor unit and the number of
indoor units that are active.
The number of units that are active can be read from the LED display in the "Monitor Mode"
procedure below.
Example:
in the following procedure there are 22 units active:
Note:
Wherever during this procedure, press the
BS1 MODE
button if something becomes unclear.
You will return to setting mode 1 (H1P=
h
"OFF").
1. Setting mode 1 (default system status)
Press the
BS1 MODE
button to switch from setting mode 1 to monitor mode.
2. Monitor mode
To check the number of indoor units, press the
BS2 SET
button 5 times
3. Monitor mode
Pressing the
BS3 RETURN
button causes the LED display to show the data on the number
of indoor units that are connected.
4. Monitor mode
Calculate the number of connected indoor units by adding the values of all (H2P~H7P)
blinking (
j
) LEDs together.
In this example: 16+4+2=
22
units
Press the
BS1 MODE
button to return to step 1, setting mode 1 (H1P=
h
"OFF").
h
OFF
i
ON
j
Blinking
Default status (normal)
Default status display
Selection status of how many
connected indoor units to display.
Displaying the number of connected
indoor units
H1P
H2P
H3P
H4P
H5P
H6P
H7P
h h i h h h h
H1P
H2P
H3P
H4P
H5P
H6P
H7P
j h h h h h h
H1P
H2P
H3P
H4P
H5P
H6P
H7P
j h h h i h i
H1P
H2P
H3P
H4P
H5P
H6P
H7P
32
16
8
4
2
1
j h j h j j h
Содержание VRV III REYQ10PY1B
Страница 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Страница 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Страница 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Страница 395: ...Piping Diagrams SiBE37 701 384 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12P 3D058154B S1NPH S2NPL ...
Страница 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Страница 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Страница 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Страница 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Страница 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Страница 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Страница 414: ...SiBE37 701 Wiring Diagrams for Reference Appendix 403 2 3 Indoor Unit FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125PVEB ...
Страница 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Страница 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Страница 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Страница 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Страница 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Страница 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Страница 447: ...Example of connection SiBE37 701 436 Appendix ...
Страница 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Страница 467: ...SiBE37 701 iv Index ...
Страница 471: ...SiBE37 701 viii Drawings Flow Charts ...