SiBE37-701
Field Setting
Test Operation
215
The numbers in the "No." column represent the number of times to press the
SET (BS2) button.
*1: Number of connected indoor units
Used to make setting of the number of indoor units connected to an outdoor
unit.
*2: Number of connected BS units
Used to make setting of the number of BS units connected to an outdoor
unit.
*3: Number of outdoor units
Used to make setting of the number of outdoor units connected to DIII-NET
that is one of the communication lines.
*4: Number of BS units
Used to make setting of the number of BS units connected to DIII-NET that is
one of the communication lines.
*5: Number of terminal units
Used to make setting of the number of indoor units connected to DIII-NET
that is one of the communication lines.
(Only available for VRV indoor units)
No.
Setting item
LED display
Data display
H1P
H2P
H3P
H4P
H5P
H6P
H7P
0
Various settings
l h h h h h h
Lower 4 digits
1
C/H unified address
l h h h h h k
Lower 6 digits
2
Low noise/demand address
l h h h h k h
3
Not used
l h h h h k k
4
Airnet address
l h h h k h h
5
Number of connected indoor units
*1
l h h h k h k
6
Number of connected BS units *2
l h h h k k h
7
Number of connected zone units
(Fixed to "0")
l h h h k k k
8
Number of outdoor units *3
l h h k h h h
9
Number of BS units *4
l h h k h h k
Lower 4 digits:
upper
10
Number of BS units *4
l h h k h k h
Lower 4 digits:
lower
11
Number of zone units
l h h k h k k
Lower 6 digits
12
Number of terminal units *5
l h h k k h h
Lower 4 digits:
upper
13
Number of terminal units *5
l h h k k h k
Lower 4 digits:
lower
14
Contents of malfunction (the
latest)
l h h k k k h
Malfunction
code table
Refer page
248.
15
Contents of malfunction
(1 cycle before)
l h h k k k k
16
Contents of malfunction
(2 cycle before)
l h k h h h h
20
Contents of retry (the latest)
l h k h k h h
21
Contents of retry (1 cycle before)
l h k h k h k
22
Contents of retry (2 cycle before)
l h k h k k h
25
Number of multi connection
outdoor units
l h k k h h k
Lower 6 digits
c. Monitor mode
<Selection of setting item>
<Confirmation on setting contents>
To enter the monitor mode, push the
MODE (BS1) button when in
“Setting mode 1”.
Push the SET (BS2) button and set
the LED display to a setting item.
Push the RETURN (BS3) button to
display different data of set items.
Push the RETURN (BS3) button and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE (BS1) button and
returns to “Setting mode 1”.
(V2765)
Содержание VRV III REYQ10PY1B
Страница 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Страница 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Страница 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Страница 395: ...Piping Diagrams SiBE37 701 384 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12P 3D058154B S1NPH S2NPL ...
Страница 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Страница 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Страница 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Страница 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Страница 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Страница 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Страница 414: ...SiBE37 701 Wiring Diagrams for Reference Appendix 403 2 3 Indoor Unit FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125PVEB ...
Страница 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Страница 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Страница 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Страница 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Страница 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Страница 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Страница 447: ...Example of connection SiBE37 701 436 Appendix ...
Страница 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Страница 467: ...SiBE37 701 iv Index ...
Страница 471: ...SiBE37 701 viii Drawings Flow Charts ...