Troubleshooting (OP: Unified ON/OFF Controller)
SiBE37-701
380
Troubleshooting
[Check 13] Vacuuming and dehydration procedure
Conduct vacuuming and dehydration in the piping system following the procedure for <Normal
vacuuming and dehydration> described below.
Furthermore, if moisture may get mixed in the piping system, follow the procedure for <Special
vacuuming and dehydration> described below.
<Normal vacuuming and dehydration>
Vacuuming and dehydration
• Use a vacuum pump that enables vacuuming up to 100.7kPa (5 torr, -755 mmHg).
• Connect manifold gauges to the service ports of liquid pipe and gas pipe and run the
vacuum pump for a period of two or more hours to conduct evacuation to -100.7kPa or
less.
• If the degree of vacuum does not reach -100.7kPa or less even though evacuation is
conducted for a period of two hours, moisture will have entered the system or refrigerant
leakage will have been caused. In this case, conduct evacuation for a period of another
one hour.
• If the degree of vacuum does not reach -100.7kPa or less even though evacuation is
conducted for a period of three hours, conduct leak tests.
Leaving in vacuum state
• Leave the compressor at the degree of vacuum of -100.7kPa or less for a period of one
hour or more, and then check to be sure that the vacuum gauge reading does not rise. (If
the reading rises, moisture may have remained in the system or refrigerant leakage may
have been caused.)
Refrigerant charge
• Purge air from the manifold gauge connection hoses, and then charge a necessary
quantity of refrigerant.
<Special vacuuming and dehydration> - In case moisture may get mixed in the piping*
Vacuuming and dehydration
• Follow the same procedure as that for 1) Normal vacuuming and dehydration described
above.
Vacuum break
• Pressurize with nitrogen gas up to 0.05MPa.
Vacuuming and dehydration
• Conduct vacuuming and dehydration for a period of one hour or more. If the degree of
vacuum does not reach -100.7kPa or less even though evacuation is conducted for a
period of two hours or more, repeat vacuum break - vacuuming and dehydration.
Leaving in vacuum state
• Leave the compressor at the degree of vacuum of -100.7kPa or less for a period of one
hour or more, and then check to be sure that the vacuum gauge reading does not rise.
Refrigerant charge
• Purge air from the manifold gauge connection hoses, and then charge a necessary
quantity of refrigerant.
∗
In case of construction during rainy reason, if dew condensation occurs in the piping due
to extended construction period, or rainwater or else may enter the piping during
construction work:
Содержание VRV III REYQ10PY1B
Страница 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Страница 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Страница 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Страница 395: ...Piping Diagrams SiBE37 701 384 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12P 3D058154B S1NPH S2NPL ...
Страница 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Страница 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Страница 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Страница 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Страница 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Страница 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Страница 414: ...SiBE37 701 Wiring Diagrams for Reference Appendix 403 2 3 Indoor Unit FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125PVEB ...
Страница 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Страница 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Страница 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Страница 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Страница 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Страница 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Страница 447: ...Example of connection SiBE37 701 436 Appendix ...
Страница 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Страница 467: ...SiBE37 701 iv Index ...
Страница 471: ...SiBE37 701 viii Drawings Flow Charts ...