Special Control
SiBE37-701
122
Function
3.3.2 Heating Oil Return Operation (including cooling / heating
simultaneous operation)
[Start conditions]
Referring to the following conditions, start heating oil return operation.
• Integral oil rise rate is reached to specified level.
• When cumulative compressor operating time exceeds 8 hours (2 hours when the power supply turns ON for
the first time)
Furthermore, the integral oil rise rate is calculated by Tc, Te, and compressor loads.
The higher the compressor operating step No., the cumulative refrigerant oil consumption increases.
*1: In case of multi outdoor unit system:
Master unit: It conducts the operation listed in the table above.
Slave units: Operating units conduct the operation listed in the table above.
Non-operating units conduct the operation listed in the table above after the "Oil returning" process.
(Non-operating units stop while in "Preparation" mode.)
Actuator
Symbol
Elect. symbol
Oil return operation
REYQ
REMQ
Compressor 1
—
M1C
M1C
Maintain load that was applied before oil return
operation.
When current circulation rate < circulation rate required
for oil return operation, turn ON the STD compressor
every 10 seconds (up to 3 units at maximum).
Compressor 2
M2C
M2C
Compressor 3
—
M3C
Outdoor unit fan 1
—
M1F
M1F
When outdoor unit heat exchanger is condenser, the
fan will run under cooling fan control.
When outdoor unit heat exchanger is evaporator, the
fan will run at the fan step 7 or 8.
Outdoor unit fan 2
M2F
M2F
Electronic expansion valve (main)
EVM
Y1E
Y3E
Y1E
20SA=ON : PI control
20SA=OFF : 418pls
Electronic expansion valve
(subcooling)
EVT
Y2E
Y5E
Y3E
PI control
Electronic expansion valve (refilling
refrigerant)
EVJ
Y4E
Y2E
80pls
Four way valve (for heat changer
selection)
20SA
Y2S
Y9S
Y3S
When outdoor unit heat exchanger is condenser, the
valve will turn OFF.
When outdoor unit heat exchanger is evaporator, the
valve will turn ON.
Four way valve (for high- and low-
pressure gas pipe selection)
20SB
Y8S
Y2S
OFF
Solenoid valve (main bypass)
SVE
Y5S
Y10S
Y6S
OFF
Solenoid valve (hot gas)
SVP
Y4S
Y5S
0pls
Solenoid valve (liquid pipe of
refrigerant regulator)
SVL
Y3S
Y4S
0pls
Solenoid valve (gas discharge pipe of
refrigerant regulator)
SVG
Y1S
Y1S
0pls
Solenoid valve (drain pipe of
refrigerant regulator)
SVO
Y7S
Y7S
0pls
Solenoid valve (discharge pipe of
refrigerant regulator)
SVT
Y6S
Y8S
0pls
End conditions
•
Pe_min<0.22MPa
•
After a lapse of 9 min.
OR
or
Содержание VRV III REYQ10PY1B
Страница 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Страница 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Страница 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Страница 395: ...Piping Diagrams SiBE37 701 384 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12P 3D058154B S1NPH S2NPL ...
Страница 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Страница 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Страница 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Страница 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Страница 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Страница 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Страница 414: ...SiBE37 701 Wiring Diagrams for Reference Appendix 403 2 3 Indoor Unit FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125PVEB ...
Страница 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Страница 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Страница 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Страница 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Страница 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Страница 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Страница 447: ...Example of connection SiBE37 701 436 Appendix ...
Страница 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Страница 467: ...SiBE37 701 iv Index ...
Страница 471: ...SiBE37 701 viii Drawings Flow Charts ...