(6) External ON/OFF input
This input is used for "ON / OFF operation" and "Protection device input" from the outside. The
input is performed from the T1-T1 terminal of the operation terminal block (X1A) in the electric
component box.
Setting Table
(7) Thermostat Switching
Differential value during thermostat ON/OFF control can be changed. (For details, refer to "6.4
Thermostat Control while in Normal Operation" on page 137.)
(8) Air Flow Setting When Heating Thermostat is OFF
This setting is used to set air flow when heating thermostat is OFF.
∗
When thermostat OFF air flow volume up mode is used, careful consideration is required
before deciding installation location. During heating operation, this setting takes precedence
over "(7) Fan Stop When Thermostat is OFF."
(9) Setting of operation mode to "AUTO"
This setting makes it possible to change differential values for mode selection while in automatic
operation mode.
The automatic operation mode setting is made by the use of the "Operation Mode Selector"
button.
F2 T1 T2
Forced stop
Input A
Mode No.
Setting
Switch No.
Setting
Position No.
Operation by input of the signal A
12 (22)
1
01
ON: Forced stop (prohibition of using the remote
controller)
OFF: Permission of using the remote controller
02
OFF
→
ON: Permission of operation
ON
→
OFF: Stop
03
ON: Operation
OFF: The system stops, then the applicable unit
indicates "A0". The other indoor units indicate "U9".
Mode No.
First Code No.
Second Code No.
Differential value
12(22)
2
01
1ºC
02
0.5ºC
Mode No.
First Code No.
Second Code No.
Contents
12 (22)
3
01
LL air flow
02
Preset air flow
Mode No.
Setting switch No.
Setting position No.
01
02
03
04
05
06
07
08
12 (22)
4
0°C
1°C
2°C
3°C
4°C
5°C
6°C
7°C
Содержание VRV III REYQ10PY1B
Страница 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Страница 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Страница 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Страница 395: ...Piping Diagrams SiBE37 701 384 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12P 3D058154B S1NPH S2NPL ...
Страница 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Страница 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Страница 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Страница 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Страница 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Страница 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Страница 414: ...SiBE37 701 Wiring Diagrams for Reference Appendix 403 2 3 Indoor Unit FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125PVEB ...
Страница 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Страница 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Страница 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Страница 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Страница 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Страница 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Страница 447: ...Example of connection SiBE37 701 436 Appendix ...
Страница 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Страница 467: ...SiBE37 701 iv Index ...
Страница 471: ...SiBE37 701 viii Drawings Flow Charts ...