Troubleshooting (OP: Unified ON/OFF Controller)
SiBE37-701
378
Troubleshooting
[Check 11] Check for overcharge of refrigerant.
In case of VRV Systems, the only way to judge as the overcharge of refrigerant is with operating
conditions due to the relationship to pressure control and electronic expansion valve control.
As information for making a judgment, refer to information provided below.
Diagnosis of overcharge of refrigerant
1. High pressure rises. Consequently, overload control is exercised to cause scant cooling
capacity.
2. The superheated degree of suction gas lowers (or the wet operation is performed).
Consequently, the compressor becomes lower in discharge pipe temperature despite of
pressure loads.
3. The supercooled degree of condensate rises. Consequently, in heating operation, the
temperature of outlet air passing through the supercooled section becomes lower.
Cooling
High pressure
Low pressure
Frequency
High-pressure
drooping control
(LP is maintained
at a constant level.)
To maintain LP, frequency
increases under the capacity
control.
HP gradually rises
with increase in
frequency.
Frequency comes to
the minimum level.
Supercooled degree
becomes higher.
(Liquid connection
pipe temperature
lowers.)
LP rises due to
reduced compressor
output.
High pressure
Low pressure
Frequency
Heating
The outdoor unit motorized valve is
closed due to the overload control.
Frequency comes to
the minimum level.
(HP is maintained
at a constant level.)
LP rises due to
reduced frequency.
To maintain HP, frequency reduces
under the capacity control.
HP drops or rises immediately
after the overload control is
complete.
LP drops due to closed
outdoor unit motorized
valve.
Hot gas bypass is activated
for LP protection, i.e.,
hunting at LP.
Higher degree of overcharge
(Degree of overcharge)
Proper quantity
Содержание VRV III REYQ10PY1B
Страница 1: ...REYQ8 48PY1B R 410A Heat Recovery 50Hz SiBE37 701 ...
Страница 111: ...Refrigerant Flow for Each Operation Mode SiBE37 701 100 Refrigerant Circuit ...
Страница 252: ...SiBE37 701 Troubleshooting by Remote Controller Troubleshooting 241 ...
Страница 395: ...Piping Diagrams SiBE37 701 384 Appendix 1 Piping Diagrams 1 1 Outdoor Unit REYQ8P 10P 12P 3D058154B S1NPH S2NPL ...
Страница 396: ...SiBE37 701 Piping Diagrams Appendix 385 REYQ14P 16P 3D058153B S2NPL S1NPH ...
Страница 397: ...Piping Diagrams SiBE37 701 386 Appendix REMQ8P 3D057743 ...
Страница 398: ...SiBE37 701 Piping Diagrams Appendix 387 REMQ10P 12P 3D057742 ...
Страница 399: ...Piping Diagrams SiBE37 701 388 Appendix REMQ14P 16P 3D057741 ...
Страница 400: ...SiBE37 701 Piping Diagrams Appendix 389 1 2 Indoor Unit FXFQ P ...
Страница 405: ...Piping Diagrams SiBE37 701 394 Appendix 1 3 BS Unit 4D057985A ...
Страница 414: ...SiBE37 701 Wiring Diagrams for Reference Appendix 403 2 3 Indoor Unit FXFQ20P 25P 32P 40P 50P 63P 80P 100P 125PVEB ...
Страница 415: ...Wiring Diagrams for Reference SiBE37 701 404 Appendix FXZQ20M 25M 32M 40M 50MV1 ...
Страница 416: ...SiBE37 701 Wiring Diagrams for Reference Appendix 405 FXCQ20M 25M 32M 63MV3 ...
Страница 417: ...Wiring Diagrams for Reference SiBE37 701 406 Appendix FXCQ40M 50M 80M 125MV3 ...
Страница 420: ...SiBE37 701 Wiring Diagrams for Reference Appendix 409 FXDQ20M 25MV3 ...
Страница 421: ...Wiring Diagrams for Reference SiBE37 701 410 Appendix FXSQ20M 25M 32M 40M 50M 63MV3 ...
Страница 422: ...SiBE37 701 Wiring Diagrams for Reference Appendix 411 FXSQ80M 100M 125MV3 ...
Страница 447: ...Example of connection SiBE37 701 436 Appendix ...
Страница 453: ...Method of Checking the Inverter s Power Transistors and Diode Modules SiBE37 701 442 Appendix ...
Страница 467: ...SiBE37 701 iv Index ...
Страница 471: ...SiBE37 701 viii Drawings Flow Charts ...