2
|
Components
Service manual
119
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
T °C
kΩ
T °C
kΩ
T °C
kΩ
T °C
kΩ
–9
–8
–7
–6
–5
–4
–3
–2
–1
106.03
100.41
95.14
90.17
85.49
81.08
76.93
73.01
69.32
21
22
23
24
25
26
27
28
29
23.91
22.85
21.85
20.90
20.00
19.14
18.32
17.54
16.80
51
52
53
54
55
56
57
58
59
6.91
6.65
6.41
6.65
6.41
6.18
5.95
5.74
5.14
0
65.84
30
16.10
60
4.87
1
2
3
4
5
6
7
8
9
62.54
59.43
56.49
53.71
51.09
48.61
46.26
44.05
41.95
31
32
33
34
35
36
37
38
39
15.43
14.79
14.18
13.59
13.04
12.51
12.01
11.52
11.06
61
62
63
64
65
66
67
68
69
4.70
4.54
4.38
4.23
4.08
3.94
3.81
3.68
3.56
Thermistor – Table B
T °C
kΩ
T °C
kΩ
T °C
kΩ
T °C
kΩ
–30
–25
–20
–15
–10
–5
0
200.20
144.32
105.38
77.90
58.25
44.0
33.6
5
10
15
20
25
30
35
25.9
20.2
15.8
12.5
10.0
8.0
6.5
40
45
50
55
60
65
70
5.3
4.3
3.6
3.0
2.5
2.1
1.8
75
80
85
90
95
1.5
1.3
1.1
0.9
0.8
5
Disconnect the thermistor connector from the appropriate PCB.
6
Measure the resistance between the appropriate pins of the thermistor
connector.
7
Check that the measured resistance value matches the resistance determined
through the measured temperature (earlier step in the procedure).