1.5.5 C9-00 – Room thermistor abnormality
Trigger
Effect
Reset
Resistance value is out of
range. Temperature
measured <–43.6°C or
>90°C.
Unit will stop operating.
Automatic reset when
resistance is within range.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the indoor unit air (room) thermistor. See
Possible cause:
Faulty indoor unit air (room) thermistor.
2
Perform a check of the indoor unit main PCB. See
Possible cause:
Faulty indoor unit main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
1.5.6 E1-00 – Outdoor unit: PCB defect
Trigger
Effect
Reset
Main PCB detects that
EEPROM is abnormal.
Unit will stop operating.
Manual reset via user
interface.
Power reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1
Perform a check of the main PCB. See
Possible cause:
Faulty main PCB.
2
Check if the power supply is conform with the regulations. See
127].
Possible cause:
▪
Faulty or disturbance of the power supply (imbalance >4%),
▪
Power drop,
▪
Short circuit.
3
Perform a check of the outdoor unit fan motor. See
92].
Possible cause:
Faulty outdoor unit fan motor.
4
Perform a check of the compressor. See