2
|
Components
Service manual
58
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
1
Remove the expansion valve motor, see
2
Remove the putty. Keep for re-use.
a
b
c
a
Putty
b
Expansion valve pipe
c
Expansion valve body
a
b
a
Expansion valve pipe
b
Expansion valve body
INFORMATION
The expansion valve and motor can have a different configuration / layout.
3
Cut the expansion valve pipes using a pipe cutter.
4
Remove the expansion valve body.
5
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.
6
Heat the ends of the expansion valve pipes using an oxygen acetylene torch
and remove the expansion valve pipe ends.
7
Stop the nitrogen supply when the piping has cooled down.
8
To install the expansion valve body, see
To install the expansion valve body
1
Install the expansion valve body in the correct location and correctly oriented.
2
Supply nitrogen to the refrigerant circuit. The nitrogen pressure MUST NOT
exceed 0.02 MPa.