2
|
Components
Service manual
74
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
Problem solved?
After all checking procedures listed above have been performed:
Is the problem solved?
Action
Yes
No further actions required.
No
Return to the troubleshooting of the
specific error and continue with the
next procedure.
2.7.2 Repair procedures
As the inverter PCB is integrated in the main PCB of the unit, see
74] for the repair procedures.
2.8 Main PCB
2.8.1 Class 20~42 units
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a power check of the main PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
101].
1
Turn ON the power of the unit.
2
Measure the voltage between the black and white wires.
Result:
The measured voltage MUST be 230 V AC.
a
b
a
Black wire
b
White wire
Содержание Sensira Series