2.8.2 Class 50~71 units
Checking procedures
INFORMATION
It is recommended to perform the checks in the listed order.
To perform a power check of the main PCB
Prerequisite:
Stop the unit operation via the user interface.
Prerequisite:
Turn OFF the respective circuit breaker.
Prerequisite:
Remove the required plate work, see
101].
1
Turn ON the power of the unit.
2
Measure the voltage between the black and white wires.
Result:
The measured voltage MUST be 230 V AC.
a
b
a
Black wire
b
White wire
Is the measured voltage on the PCB
correct?
Action
Yes
84] of the PCB and
continue with the next procedure.
No
Continue with the next step.
3
Check the power supply to the unit, see
Does the unit receive power?
Action
Yes
89].
No
Adjust the power supply to the unit, see
128].
To check the HAP LED of the main PCB
Prerequisite:
First check the power supply to the main PCB, see
84].
1
Locate the HAP LED on the main PCB.