2
|
Components
Service manual
39
FTXF20~71A + FTXF20~25B + FTXF20~42C + ATXF20~71A + ATXF20~42C
+ RXF20~71A + RXF20~60B + RXF20~42C + ARXF20~71A + ARXF20~42C
Split Sensira R32
ESIE18-12E – 2021.02
12
With the 4‑way valve connector connected to the PCB, measure the voltage
on the 4‑way valve connection of the PCB.
Result:
The measured voltage MUST be:
Class
Voltage
Class 20~42
12 V DC when operating in
Heating
mode
0 V DC when operating in
Cooling
mode
Class 50~71
220~240 V AC when operating in
Heating
mode
0 V AC when operating in
Cooling
mode
Is the measured voltage correct?
Action
Yes
Perform a position check of the 4-way
valve, see
No
Perform a check the main PCB, see
To perform a position check of the 4-way valve
1
First perform an electrical check of the 4‑way valve, see
When outdoor temperature is mild and unit can switch between heating and
cooling
INFORMATION
This procedure is ONLY possible when the outdoor temperature is within the
temperature range for both
Heating
and
Cooling
operation mode. See the
databook on Business Portal for the temperature range of the operation modes.
2
Activate
Heating
operation via the user interface.
INFORMATION
It is recommended to connect the service monitoring tool to the unit and verify the
operation mode of the 4-way valve.
3
Check with a contact thermometer (or by touching) if the flow through the 4-
way valve corresponds with the flow shown in the flow diagram. (See
Is the flow correct?
Action
Yes
Skip the next step of this procedure.
No
Perform the next step of this procedure.
4
Connect a manifold to one of the service ports of the refrigerant circuit and
check the pressure (suction, discharge). Compare with normal operation
conditions of the unit.