Table 62: Drive Control Terminal Descriptions
X1
Drive Control Terminal Description
Analog I/O
1
SCR
Terminal for signal cable screen . (Connected internally to chassis ground .)
2
AI1
Analog input channel 1, programmable . Default
2
= external reference . Resolution 0 .1%, accuracy ±1% .
J1:AI1 OFF: 0(2)…10 V (Ri = 312 kΩ)
or, for OFF
for ON
J1:AI1 ON: 0(4)…20 mA (Ri = 100 Ω)
3
AGND
Analog input circuit common (connected internally to chassis gnd. through 1 MΩ).
4
+10 V
Potentiometer reference source: 10 V ±2%, max. 10 mA (1kΩ < R < 10kΩ).
5
AI2
Analog input channel 2, programmable . Default
2
= PID feedback . Resolution 0 .1%, accuracy ±1% .
J1:AI2 OFF: 0(2)…10 V (Ri = 312 kΩ)
or, for OFF
for ON
J1:AI2 ON: 0(4)…20 mA (Ri = 100 Ω)
6
AGND
Analog input circuit common (connected internally to chassis gnd. through 1 MΩ).
7
AO1
Analog output, programmable . Default
2
= frequency. 0…20 mA (load < 500 Ω).
8
AO2
Analog output, programmable . Default
2
= current. 0…20 mA (load < 500 Ω).
9
AGND
Analog output circuit common (connected internally to chassis gnd. through 1 MΩ).
Digital Inputs
1
10
+24V .
Auxiliary voltage output 24 VDC / 250 mA (reference to GND), short circuit protected
11
GND
Auxiliary voltage output common (connected internally as floating).
12
DCOM
Digital input common. To activate a digital input, there must be ≥+10 V (or ≤-10 V) between that input and DCOM. The 24 V may be
provided by the MD5 (X1-10) or by an external 12…24 V source of either polarity .
13
DI1
Digital input 1, programmable . Default
2
= start/stop .
14
DI2
Digital input 2, programmable . Default
2
= not configured.
15
DI3
Digital input 3, programmable . Default
2
= constant (preset) speed .
16
DI4
Digital input 4, programmable . Default
2
= safety interlock .
17
DI5
Digital input 5, programmable . Default
2
= not configured.
18
DI6
Digital input 6, programmable . Default
2
= not configured.
Relay Outputs
19
RO1C
Relay output 1, programmable . Default
2
= Ready
Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)
20
RO1A
21
RO1B
22
RO2C
Relay output 2, programmable . Default2 = Running
Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)
23
RO2A
24
RO2B
25
RO3C
Relay output 3, programmable . Default2 = Fault (-1)
Maximum: 250 VAC / 30 VDC, 2 A
Minimum: 500 mW (12 V, 10 mA)
26
RO3A
27
RO3B
1 Digital input impedance 1.5 kΩ. Maximum voltage for digital inputs is 30 V.
2 Default values depend on the macro used. Values specified are for the HVAC default macro. See
Application Macros on page 9
.
You can wire the digital input terminals in either a PNP or NPN
configuration.
Serial Communications
Terminals 28…32 provide RS485 serial communication
connections used to control or monitor the drive from a fieldbus
controller . See
Embedded Fieldbus on page 45
for details .
OM 1191 • MD5 VFD
86
www .DaikinApplied .com
T
eChniCal
d
aTa