Group 16: System Controls
This group defines a variety of system level locks, resets and enables.
Table 11: Group 16: System Controls
Code Description
Range
Resolution
Default
S
1601 RUN ENABLE
-6…7
1
0 (NOT
SEL)
Selects the source of the run enable signal .
0 = NOT SEL – Allows the drive to start without an external run enable signal .
1 = DI1 – Defines digital input DI1 as the run enable signal.
• This digital input must be activated for run enable .
• If the voltage drops and de-activates this digital input, the drive will coast to stop and not start until the run enable signal resumes .
2…6 = DI2…DI6 – Defines digital input DI2…DI6 as the run enable signal.
• See DI1 above .
7 = COMM – Assigns the fieldbus Command Word as the source for the run enable signal.
• Bit 6 of the Command Word 1 (parameter 0301) activates the run disable signal .
• See fieldbus user’s manual for detailed instructions.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the run enable signal.
• This digital input must be de-activated for run enable .
• If this digital input activates, the drive will coast to stop and not start until the run enable signal resumes .
-2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the run enable signal.
• See DI1(INV) above .
1604 FAULT RESET SEL
-6…8
1
0 (KEYPAD)
Selects the source for the fault reset signal . The signal resets the drive after a fault trip if the cause of the fault no longer exists .
0 = KEYPAD – Defines the control panel as the only fault reset source.
• Fault reset is always possible with control panel .
1 = DI1 – Defines digital input DI1 as a fault reset source.
• Activating the digital input resets the drive .
2…6 = DI2…DI6 – Defines digital input DI2…DI6 as a fault reset source.
• See DI1 above .
7 = START/STOP – Defines the Stop command as a fault reset source.
• Do not use this option when fieldbus communication provides the start, stop and direction commands.
8 = COMM – Defines the fieldbus as a fault reset source.
• The Command Word is supplied through fieldbus communication.
• The bit 4 of the Command Word 1 (parameter 0301) resets the drive .
-1 = DI1(INV) – Defines an inverted digital input DI1 as a fault reset source.
• De-activating the digital input resets the drive .
-2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as a fault reset source.
• See DI1(INV) above .
1607 PARAM . SAVE
0, 1
1
0 (DONE)
Saves all altered parameters to permanent memory .
• Parameters altered through a fieldbus are not automatically saved to permanent memory. To save, you must use this parameter.
• If 1602 PARAMETER LOCK = 2 (NOT SAVED), parameters altered from the control panel are not saved . To save, you must use this parameter .
• If 1602 PARAMETER LOCK = 1 (OPEN), parameters altered from the control panel are stored immediately to permanent memory .
0 = DONE – Value changes automatically when all parameters are saved .
1 = SAVE… – Saves altered parameters to permanent memory .
OM 1191 • MD5 VFD 26 www .DaikinApplied .com