Table 25 continued:
Serial Communication Configuration
Code
Description
EFB Protocol Reference
Modbus
N2
FLN
BACnet
5305
EFB CTRL PROFILE
Selects the communication profile
used by the EFB protocol .
0 = Daikin DRV LIM – Operation
of Control/Status Words
conform to Daikin Drives
Profile (limited), as used in
ACH400/550 .
1 = DCU PROFILE – Operation of
Control/Status Words conform
to 32-bit DCU Profile.
2 = Daikin DRV FULL – Operation
of Control/Status Words
conform to Daikin Drives
Profile (full).
When this protocol is
selected, the default value
for this parameter is: 0
N/A . When this protocol is selected, the default value for this parameter is: 0 . Changing
the value for this parameter has no affect on this protocol’s behavior .
5306
EFB OK MESSAGES
This parameter indicates the number of valid application messages received at this drive . This count does not include
MS/TP token passing and polling messages . (For such messages, see 5316) .
5307
EFB CRC ERRORS
This parameter indicates the number of CRC errors detected, in either the header or data CRCs .
5308
EFB UART ERRORS
This parameter indicates the number of UART-related errors (framing, parity) detected .
5309
EFB STATUS
This parameter indicates the internal status of the EFB Protocol as follows:
• IDLE – EFB Protocol is configured but not receiving messages.
• TIMEOUT – Time between valid messages has exceeded the interval set by parameter 3019 .
• OFFLINE – EFB Protocol is receiving messages NOT addressed to this drive .
• ONLINE – EFB Protocol is receiving messages addressed to this drive .
• RESET – EFB Protocol is in reset .
• LISTEN ONLY – EFB Protocol is in listen-only mode .
5310
EFB PAR10
Not used for Comm setup .
Sets the response turnaround time in milliseconds in addition to any fixed delay imposed
by the protocol . When this protocol is selected, the default value is:
3 ms
0 ms
5 ms
5311
EFB PAR11
Not used for Comm setup .
This parameter, together
with parameter 5317, EFB
PAR 17, sets BACnet
Device Object Instance IDs:
• For the range 1 to 65,535:
Thips parameter sets the
ID directly (5317 must
be 0) . For example, the
following values set the ID
to 49134: 5311 = 49134
and 5317 = 0 .
• For IDs > 65,335: The
ID equals 5311’s value
plus 10,000 times 5317’s
value . For examle, the
following values set the
ID to 71234: 5311 = 1234
and 5317 = 7 .
5314
EFB PAR14
Not used for Comm setup .
5315
EFB PAR15
Not used for Comm setup .
5316
EFB PAR 16
Not used for Comm setup .
This parameter indicates
the count of MS/TP tokens
passed to this drive .
5317
EFB PAR17
This parameter works
with parameter 5311 to
set BACnet Device Object
Instance IDs . See parameter
5311,
page 38
.
NOTE:
After any changes to the communication settings,
protocol must be reactivated by either cycling the
drive power, or by setting parameter 5302 EFB
STATION ID to 0 and then restoring the station ID
(5302) or use Reinitialize Device Service
e
Mbedded
f
ieldbUs
www .DaikinApplied .com 49
OM 1191 • MD5 VFD