Relay Output Control
Using the fieldbus for relay output control requires:
•
Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
For example:
To control relays 1 and 2 using serial
communication:
Set parameters 1401 RELAY OUTPUT 1 and 1402 RELAY
OUTPUT 1 = 35 (COMM) .
Then, for example using N2:
• To turn Relay 1 On: Force object B07 to On .
• To turn Relay 2 On: Force object B08 to On .
• To turn both Relay 1 and 2 On: Force objects B07 and
B08 On .
NOTE:
Relay status feedback occurs without configuration
as defined below.
Table 29: Relay Output Control Parameters
Drive Parameter
Value
Setting
Protocol Reference
Modbus
N2
FLN
BACnet
Daikin DRV
DCU PROFILE
1401
RELAY
OUTPUT 1
35 (COMM)
Relay Output
1 controlled by
fieldbus.
40134 bit 0 or 00033
BO7
40
BO0
1402
RELAY
OUTPUT 2
35 (COMM)
Relay Output
2 controlled by
fieldbus.
40134 bit 1 or 00034
BO8
41
BO1
1403
RELAY
OUTPUT 3
35 (COMM)
Relay Output
3 controlled by
fieldbus.
40134 bit 2 or 00035
BO9
42
BO2
1410
1
RELAY
OUTPUT 4
35 (COMM)
Relay Output
4 controlled by
fieldbus.
40134 bit 3 or 00036
BO10
43
BO3
1411
1
RELAY
OUTPUT 5
35 (COMM)
Relay Output
5 controlled by
fieldbus.
40134 bit 4 or 00037
BO11
44
BO4
1412
1
RELAY
OUTPUT 6
35 (COMM)
Relay Output
6 controlled by
fieldbus.
40134 bit 5 or 00038
BO12
45
BO5
0122
RO 1-3 STATUS
Relay 1…3
status .
40122
0122
BI4… BI6
76… 78
BI0… BI2
0123
RO 4-6 STATUS
Relay 4…6
status .
40123
0123
BI7… BI9
79… 81
BI3… BI5
1 . More than 3 relays requires the addition of a relay extension module .
OM 1191 • MD5 VFD 52 www .DaikinApplied .com