![Daikin MD5 Скачать руководство пользователя страница 72](http://html.mh-extra.com/html/daikin/md5/md5_operation-manual_501838072.webp)
Diagnostics – FBA
Fault Handling
The MD5 provides fault information as follows:
• The control panel display shows a fault code and text .
See
page 74
for a complete description .
• Parameters 0401 LAST FAULT, 0402 PREVIOUS
FAULT1 and 0403 PREVIOUS FAULT2 store the most
recent faults .
•
For fieldbus access, the drive reports faults as a
hexadecimal value, assigned and coded according to
the DRIVECOM specification. See table below. Not
all profiles support requesting fault codes using this
specification. For profiles that support this specification,
the profile documentation defines the proper fault request
process .
Serial Communication Diagnostics
Besides the drive fault codes, the FBA module has diagnostic
tools . Refer to the user’s manual supplied with the FBA
module .
Table 53: Drive Fault Code
Drive Fault Code
Fieldbus Fault Code
(DRIVECOM specification)
Drive Fault Code
Fieldbus Fault Code
(DRIVECOM specification)
1
OVERCURRENT
2310h
33
EFB 3
FF94h
2
DC OVERVOLT
3210h
34
MOTOR PHASE
FF56h
3
DEV OVERTEMP
4210h
35
OUTPUT WIRING
FF95h
4
SHORT CIRC
2340h
36
INCOMP SWTYPE
630Fh
5
Reserved
FF6Bh
101
SERF CORRUPT
FF55h
6
DC UNDERVOLT
3220h
102
Reserved
FF55h
7
AI1 LOSS
8110h
103
SERF MACRO
FF55h
8
AI2 LOSS
8110h
104
Reserved
FF55h
9
MOT TEMP
4310h
105
Reserved
FF55h
10
PANEL LOSS
5300h
201
DSP T1 OVERLOAD
6100h
11
ID RUN FAIL
FF84h
202
DSP T2 OVERLOAD
6100h
12
MOTOR STALL
7121h
203
DSP T3 OVERLOAD
6100h
14
EXTERNAL FLT 1
9000h
204
DSP STACK ERROR
6100h
15
EXTERNAL FLT 2
9001h
205
Reserved
5000h
16
EARTH FAULT
2330h
206
OMIO ID ERROR
5000h
17
UNDERLOAD
FF6Ah
207
EFB LOAD ERR
6100h
18
THERM FAIL
5210h
1000
PAR HZRPM
6320h
19
OPEX LINK
7500h
1001
PAR PFAREFNG
6320h
20
OPEX PWR
5414h
1002
Reserved (obsolete)
6320h
21
CURR MEAS
2211h
1003
PAR AI SCALE
6320h
22
SUPPLY PHASE
3130h
1004
PAR AO SCALE
6320h
23
ENCODER ERR
7301h
1005
PAR PCU 2
6320h
24
OVERSPEED
7310h
1006
EXT ROMISSING
6320h
25
Reserved
FF80h
1007
PAR FBUSMISSING
6320h
26
DRIVE ID
5400h
1008
PAR PFAWOSCALAR
6320h
27
CONFIG FILE
630Fh
1009
PAR PCU 1
6320h
28
SERIAL 1 ERR
7510h
1010
PAR PFA OVERRIDE
6320h
29
EFB CONFIG FILE
6306h
1011
PAR OVERRIDE PARS
6320h
30
FORCE TRIP
FF90h
1012
PAR PFC IO 1
6320h
31
EFB 1
FF92h
1013
PAR PFC IO 2
6320h
32
EFB 2
FF93h
1014
PAR PFC IO 3
6320h
OM 1191 • MD5 VFD 72 www .DaikinApplied .com