Status Information
Table 1: Status Information
Top .
The top line of the LCD display shows the basic status
information of the drive .
•
HAND
– Indicates that the drive control is local, that is,
from the control panel .
•
AUTO
– Indicates that the drive control is remote, such
as the basic I/O (X1) or fieldbus.
• – Indicates the drive and motor rotation status as
follows:
Upper right
– shows the active reference .
Middle .
Using
Group 34: Panel Display
, the middle of the LCD
display can be configured to display:
• One to three parameter values
– The default display shows
parameters 0103 (OUTPUT
FREQ) in percentages, 0104
(CURRENT) in amperes and
0120 (AI1) in milliamperes .
—
Use parameters 3401, 3408, and 3415, see
page
34
, to select the parameters (from Group 01) to
display . Entering “parameter” 0100 results in no
parameter displayed .
For example,
if 3401 = 0100
and 3415 = 0100, then only the parameter specified
by 3408 appears in the Control Panel display .
—
You can also scale each parameter in the display, for
example, to convert the motor speed to a display of
conveyor speed . Parameters 3402…3405 scale the
parameter specified by 3401, parameters 3409…3412
scale the parameter specified by 3408, etc.
• A bar meter rather than one of the parameter values .
—
Enable bar graph displays
using parameters 3404,
3411 and 3418 .
Bottom .
The bottom of the LCD
display shows:
•
Lower corners
– show the functions currently assigned
to the two soft keys .
•
Lower middle
– displays the current time (if configured to
show the time) .
Operating the Drive
Auto/Hand
– The very first time the drive is powered up, it is
in the auto control (AUTO)
mode, and is controlled from the
Control terminal block X1 .
To switch to hand control (HAND) and control the drive using
the control panel, press and hold the
or
button .
• Pressing the HAND button switches the drive to hand
control while keeping the drive running .
• Pressing the OFF button switches to hand control and
stops the drive .
To switch back to auto control (AUTO), press and hold the
button .
Hand/Auto/Off
– To start the drive press the HAND or AUTO
buttons, to stop the drive press the OFF button .
Reference
– To modify the reference (only possible if the
display in the upper right corner is in reverse video) press the
UP or DOWN buttons (the reference changes immediately) .
The reference can be modified in the local control mode
(HAND/OFF), and can be parameterized (using
Group 11:
Reference Select
) to also allow modification in the remote
control mode .
NOTE:
The Start/Stop, Shaft direction and Reference
functions are only valid in local control (HAND/OFF)
mode .
Control Panel Display
Significance
Rotating arrow
(clockwise or counterclockwise)
• Drive is running and at setpoint
• Shaft direction is forward or reverse
Rotating dotted arrow blinking
Drive is running but not at setpoint
Stationary dotted arrow
Start command is present, but motor
is not running . E .g . start enable is
missing .
OM 1191 • MD5 VFD