Table 19 continued: Group 36: Timed Functions
3603 STOP TIME 1
00:00:00…23:59:58
2 s
12:00:00 AM
Defines the daily stop time.
• The time can be changed in steps of 2 seconds .
• If the parameter value is 09:00:00, the timer is deactivated at 9 a .m .
3604 START DAY 1
1…7
1
1 (MONDAY)
Defines the weekly start day.
1 = MONDAY…7 = SUNDAY
• If parameter value is 1, timer 1 weekly is active from Monday midnight (00:00:00) .
3605 STOP DAY 1
1…7
1
1 (MONDAY)
Defines weekly stop day.
1 = MONDAY…7 = SUNDAY
• If parameter value is 5, timer 1 weekly is deactivated on Friday midnight (23:59:58) .
3606 START TIME 2
00:00:00…23:59:58
2 s
12:00:00 AM
Defines timer2 daily start time.
• See parameter 3602 .
3607 STOP TIME 2
00:00:00…23:59:58
2 s
12:00:00 AM
Defines timer 2 daily stop time.
• See parameter 3603 .
3608 START DAY 2
1…7
1
1 (MONDAY)
Defines timer 2 weekly start day.
• See parameter 3604 .
3609 STOP DAY 2
1…7
1
1 (MONDAY)
Defines timer 2 weekly stop day.
• See parameter 3605 .
3610 START TIME 3
00:00:00…23:59:58
2 s
12:00:00 AM
Defines timer 3 daily start time.
• See parameter 3602 .
3611 STOP TIME 3
00:00:00…23:59:58
2 s
12:00:00 AM
Defines timer 3 daily stop time.
• See parameter 3603 .
3612 START DAY 3
1…7
1
1 (MONDAY)
Defines timer 3 weekly start day.
• See parameter 3604 .
3613 STOP DAY 3
1…7
1
1 (MONDAY)
Defines timer 3 weekly stop day.
• See parameter 3605 .
3614 START TIME 4
00:00:00…23:59:58
2 s
12:00:00 AM
Defines timer 4 daily start time.
• See parameter 3602 .
3615 STOP TIME 4
00:00:00…23:59:58
2 s
12:00:00 AM
Defines timer 4 daily stop time.
• See parameter 3603 .
3616 START DAY 4
1…7
1
1 (MONDAY)
Defines timer 4 weekly start day.
• See parameter 3604 .
3617 STOP DAY 4
1…7
1
1 (MONDAY)
Defines timer 4 weekly stop day.
• See parameter 3605 .
3622 BOOSTER SEL
-6…6
1
0 (NOT SEL)
Selects the source for the booster signal .
0 = NOT SEL – Booster signal is disabled .
1 = DI1 – Defines DI1 as the booster signal.
2…6 = DI2…DI6 – Defines DI2…DI6 as the booster signal.
-1 = DI1(INV) – Defines an inverted digital input DI1 as the booster signal.
-2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the booster signal.
3623 BOOSTER TIME
00:00:00…23:59:58
2 s
00:00:00
Defines the booster ON time. Time is started when booster sel signal is released. If parameter value is 01:30:00, booster is active for 1 hour and 30 minutes
after activation DI is released .
P
araMeTers
www .DaikinApplied .com 37
OM 1191 • MD5 VFD