Group 34: Panel Display
This group defines the content for control panel display (middle area), when the control panel is in the Output mode.
Table 18: Group 34: Panel Display
Code Description
Range
Resolution
Default
S
3401 SIGNAL1 PARAM
100…178
1
103
(OUTPUT
FREQ)
Selects the first parameter (by number) displayed on the control panel.
• Definitions in this group define display content when the control panel is in the control mode.
• Any parameter number in Group 01: OPERATING DATA can be selected .
• Using the following parameters, the display value can be scaled, converted to convenient units and/or
displayed as a bar graph .
• The figure identifies selections made by parameters in this group.
• If just one or two parameters are selected for display, that is just one or two of the values of
parameters 3401 SIGNAL1 PARAM, 3408 SIGNAL2 PARAM and 3415 SIGNAL3 PARAM are other
than 100 (NOT SELECTED), the number and name of each displayed parameter are shown in
addition to the value .
100 = NOT SELECTED – First parameter not displayed .
101…178 – Displays parameter 0101…0178 . If parameter does not exist, the display shows “n .a .” .
3404 OUTPUT1 DSP FORM
0…9
1
5 (+0 .0)
Defines the decimal point location for the first display parameter.
0…7 – Defines the decimal point location.
• Enter the number of digits desired to the right of the decimal point .
• See the table for an example using pi (3 .14159) .
8 = BAR METER – Specifies a bar meter display.
9 = DIRECT – Decimal point location and units of measure are identical to the source signal . See
Group 01: Operating Data on page 13
parameter listing in
section Complete parameter list on page 1-67 for resolution (which indicates the decimal point location) and the units of measure .
3404 value Display
Range
0
+ 3 .0
-32768…+32767 (Signed)
1
+ 3 .1
2
+ 3 .14
3
+ 3 .142
4
3 .0
0…65535 (Unsigned)
5
3 .1
6
3 .14
7
3 .142
8
Bar meter displayed .
9
Decimal point location and units as for the source signal .
3405 OUTPUT1 UNIT
0…127
1
121 (%SP)
Selects the units used with the first display parameter.
Note:
Parameter is not effective if parameter 3404 OUTPUT1 DSP FORM = 9 (DIRECT) .
0 = NO UNIT 9 = °C
18 = MWh
27 = ft
36 = l/s
45 = Pa
54 = lb/m
63 = Mrev
1 = A
10 = lb ft
19 = m/s
28 = MGD
37 = l/min
46 = GPS 55 = lb/h
64 = d
2 = V
11 = mA
20 = m3/h
29 = inHg
38 = l/h
47 = gal/s
56 = FPS
65 = inWC
3 = Hz
12 = mV
21 = dm3/s
30 = FPM
39 = m3/s
48 = gal/m 57 = ft/s
66 = m/min
4 = %
13 = kW
22 = bar
31 = kb/s
40 = m3/m
49 = gal/h 58 = inH2O 67 = Nm
5 = s
14 = W
23 = kPa
32 = kHz
41 = kg/s
50 = ft3/s
59 = in wg 68 = Km3/h
6 = h
15 = kWh
24 = GPM
33 = ohm
42 = kg/m
51 = ft3/m 60 = ft wg
7 = rpm
16 = °F
25 = PSI
34 = ppm
43 = kg/h
52 = ft3/h
61 = lbsi
8 = kh
17 = hp
26 = CFM
35 = pps
44 = mbar
53 = lb/s
62 = ms
The following units are useful for the bar display .
117 = %ref 119 = %dev 121 = % SP 123 = Iout 125 = Fout 127 = Vdc
118 = %act 120 = %LD 122 = %FBK 124 = Vout 126 = Tout
OM 1191 • MD5 VFD 34 www .DaikinApplied .com