Group 64: Load Analyzer
This group defines the load analyzer, which can be used for analyzing the customer’s process and sizing the drive and the motor.
The peak value is logged at 2 ms level, and the distribution loggers are updated on 0 .2 s (200 ms) time level . Three different values
can be logged .
1 . Amplitude logger 1: The measured current is logged continuously . The distribution as a percentage of the nominal current
I
2
n
is shown in ten classes .
2 . Peak value logger: One signal in group 1 can be logged for the peak (maximum) value . The peak value of the signal, peak
time (time when the peak value was detected) as well the frequency, current and DC voltage at the peak time are shown .
3 . Amplitude logger 2: One signal in group 1 can be logged for amplitude distribution . The base value (100% value) can be set
by the user .
The first logger cannot be reset. The other two loggers can be reset by a user defined method. They are also reset if either of the
signals or the peak value filter time is changed.
Table 21: Group 64: Load Analyzer
Code Description
Range
Resolution
Default
S
6401 PVL SIGNAL
100…178
1
103
(OUTPUT
FREQ)
Defines (by number) the signal logged for the peak value.
• Any parameter number in
Group 01: Operating Data on page 13
can be selected . Eg 102 = parameter 0102 SPEED .
100 = NOT SELECTED – No signal (parameter) logged for the peak value .
101…178 – Logs parameter 0101…0178 .
6402 PVL FILTER TIME
0 .0…120 .0 s
0 .1 s
0 .1 s
Defines the filter time for peak value logging.
• 0 .0…120 .0 – Filter time (seconds) .
6403 LOGGERS RESET
-6…7
1
0
(NOT SEL)
Defines the source for the reset of peak value logger and amplitude logger 2.
0 = NOT SEL – No reset selected .
1 = DI1 – Reset loggers on the rising edge of digital input DI1 .
2…6 = DI2…DI6 – Reset loggers on the rising edge of digital input DI2…DI6 .
7 = RESET – Reset loggers . Parameter is set to NOT SEL .
-1 = DI1(INV) – Reset loggers on the falling edge of digital input DI1 .
-2…-6 = DI2(INV) …DI6(INV) – Reset loggers on the falling edge of digital input DI2…DI6 .
6404 AL2 SIGNAL
101…178
1
103
(OUTPUT
FREQ)
Defines the signal logged for amplitude logger 2.
• Any parameter number in
Group 01: Operating Data
can be selected . Eg 102 = parameter 0102 SPEED .
100 = NOT SELECTED – No signal (parameter) logged for amplitude distribution (amplitude logger 2) .
101…178 – Logs parameter 0101…0178 .
6405 AL2 SIGNAL BASE
Depends on
selection
—
60 .0 Hz
Defines the base value from which the percentage distribution is calculated.
• Representation and default value depends on the signal selected with parameter 6404 AL2 SIGNAL .
6406 PEAK VALUE
—
—
—
Detected peak value of the signal selected with parameter 6401 PVL SIGNAL .
6407 PEAK TIME 1
Date dd .mm .yy
/ power-on time
in days
1 d
—
Date of the peak value detection .
• Format: Date if the real time clock is operating (dd .mm .yy) . / The number of days elapsed after the power-on if the real time clock is not used,
or was not set (xx d) .
6408 PEAK TIME 2
Time hh .mm .ss
2 s
—
Time of the peak value detection .
• Format: hours:minutes:seconds .
6409 CURRENT AT PEAK
0 .0…6553 .5 A
0 .1 A
—
Current at the moment of the peak value (amperes) .
6410 UDC AT PEAK
0…65535 V
1 V
—
DC voltage at the moment of the peak value (volts) .
P
araMeTers
www .DaikinApplied .com 39
OM 1191 • MD5 VFD