Table 10 continued: Group 12: Constant Speeds
Code Description
Range
Resolution
Default
S
-7 = DI1,2(INV) – Selects one of three Constant Speeds (1…3) using DI1 and DI2 .
• Inverse operation uses two digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
DI1
DI2
Function
1
1
No constant speed
0
1
Constant speed 1 (1202)
1
0
Constant speed 2 (1203)
0
0
Constant speed 3 (1204)
-8 = DI2,3(INV) – Selects one of three Constant Speeds (1…3) using DI2 and DI3 .
• See above (DI1,2(INV)) for code .
-9 = DI3,4(INV) – Selects one of three Constant Speeds (1…3) using DI3 and DI4 .
• See above (DI1,2(INV)) for code .
-10 = DI4,5(INV) – Selects one of three Constant Speeds (1…3) using DI4 and DI5 .
• See above (DI1,2(INV)) for code .
-11 = DI5,6(INV) – Selects one of three Constant Speeds (1…3) using DI5 and DI6 .
• See above (DI1,2(INV)) for code .
-12 = DI1,2,3(INV) – Selects one of seven Constant Speeds (1…7) using DI1, DI2 and DI3 .
• Inverse operation uses three digital inputs, as defined below (0 = DI de-activated, 1 = DI activated):
DI1
DI2
DI3
Function
1
1
1
No constant speed
0
1
1
Constant speed 1 (1202)
1
0
1
Constant speed 2 (1203)
0
0
1
Constant speed 3 (1204)
-13 = DI3,4,5(INV) – Selects one of seven Constant Speeds (1…7) using DI3, DI4 and DI5 .
• See above (DI1,2,3(INV)) for code .
-14 = DI4,5,6(INV) – Selects one of seven Constant Speeds (1…7) using DI4, DI5 and DI6 .
• See above (DI1,2,3(INV)) for code .
1209
TIMED MODE SEL
1, 2
1
2
(CS1/2/3/4)
Defines timed function activated constant speed mode. Timed function can be used to change between the external reference and constant speeds when
parameter 1201 CONST SPEED SEL = 15…18 (TIMED FUNC 1…4) or 19 (TIMED FUN1&2) .
1 = EXT/CS1/2/3
• If parameter 1201 = 15…18 (TIMED FUNC 1…4), selects an external speed when this timed function (1…4) is not active and selects Constant speed 1
when it is active .
TIMED FUNCTION 1…4
Function
0
External reference
1
Constant speed 1 (1202)
• If parameter 1201 = 19 (TIMED FUN1&2), selects an external speed when neither timed function is active, selects Constant speed 1 when only Timed
function 1 is active, selects Constant speed 2 when only Timed function 2 is active and selects Constant speed 3 when both Timed functions 1 and 2
are active .
TIMED FUNCTION 1
TIMED FUNCTION 2
Function
0
0
External reference
1
0
Constant speed 1 (1202)
0
1
Constant speed 2 (1203)
1
1
Constant speed 3 (1204)
2 = CS1/2/3/4
• If parameter 1201 = 15…18 (TIMED FUNC 1…4), selects Constant speed 1 when this timed function (1…4) is not active and selects Constant speed 2
when it is active .
TIMED FUNCTION 1…4
Function
0
Constant speed 1 (1202)
1
Constant speed 2 (1203)
• If parameter 1201 = 19 (TIMED FUN1&2), selects Constant speed 1 when neither timed function is active, selects Constant speed 2 when only Timed
function 1 is active, selects Constant speed 3 when only Timed function 2 is active and selects Constant speed 4 when both Timed functions 1 and 2
are active .
TIMED FUNCTION 1
TIMED FUNCTION 2
Function
0
0
Constant speed 1 (1202)
1
0
Constant speed 2 (1203)
0
1
Constant speed 3 (1204)
1
1
Constant speed 4 (1205)
P
araMeTers
www .DaikinApplied .com 25
OM 1191 • MD5 VFD