Miscellaneous Drive Control
Using the fieldbus for miscellaneous drive control requires:
•
Drive parameter values set as defined below.
• Fieldbus controller supplied reference word(s) in the
appropriate location. (The location is defined by the
Protocol Reference, which is protocol dependent .)
Table 28: Miscellaneous Drive Control Parameters
Drive Parameter
Value
Setting
Protocol Reference
Modbus
N2
FLN
BACnet
Daikin DRV
DCU PROFILE
1601
RUN ENABLE
7 (COMM) (Not
Recommended)
Run enable by
fieldbus.
40001 bit 3
40031 bit 6
(inverted)
BO4
35
BV12
1604
FAULT RESET
SEL
8 (COMM)
Fault reset by
fieldbus.
40001 bit 7
40031 bit 4
BO6
94
BV14
1606
LOCAL LOCK
8 (COMM)
Source for local
lock selection is
the fieldbus.
Does not apply
40031 bit 14
1607
PARAM SAVE
1 (SAVE)
Saves altered
parameters to
memory (then
value returns
to 0) .
41607
40032 bit 2
BO18
N/A
1
1608
START ENABLE 1
7 (COMM) (Not
Recommended)
Source for
start enable 1
is the fieldbus
Command word .
Does not apply .
40032 bit 2
BV20
1609
START ENABLE 2
7 (COMM) (Not
Recommended)
Source for
start enable 2
is the fieldbus
Command word .
40032 bit 3
BV21
2013
MIN TORQUE SEL
7 (COMM)
Source for
minimum torque
selection is the
fieldbus.
40031 bit 15
2014
MAX TORQUE
SEL
7 (COMM)
Source for
maximum torque
selection is the
fieldbus.
2201
ACC/DEC 1/2 SEL
7 (COMM)
Source for ramp
pair selection is
the fieldbus.
40031 bit 10
1 . Use Memorize Point command .
e
Mbedded
f
ieldbUs
www .DaikinApplied .com 51
OM 1191 • MD5 VFD