BACnet Protocol Technical Data
Binary Input Object Instance Summary
The following table summarizes the Binary Input Objects supported:
Table 37: Binary Input Objects
Instance ID Object Name
Description
Active/Inactive Text
Present Value Access Type
BI0
RO 1 ACT
This object indicates the status of Relay Output 1 .
ON/OFF
R
BI1
RO 2 ACT
This object indicates the status of Relay Output 2 .
ON/OFF
R
BI2
RO 3 ACT
This object indicates the status of Relay Output 3 .
ON/OFF
R
BI3
RO 4 ACT
This object indicates the status of Relay Output 4 (requires OREL-01 option) .
ON/OFF
R
BI4
RO 5 ACT
This object indicates the status of Relay Output 5 (requires OREL-01 option)
ON/OFF
R
BI5
RO 6 ACT
This object indicates the status of Relay Output 6 (requires OREL-01 option)
ON/OFF
R
BI6
DI 1 ACT
This object indicates the status of Digital Input 1 .
ON/OFF
R
BI7
DI 2 ACT
This object indicates the status of Digital Input 2 .
ON/OFF
R
BI8
DI 3 ACT
This object indicates the status of Digital Input 3 .
ON/OFF
R
BI9
DI 4 ACT
This object indicates the status of Digital Input 4 .
ON/OFF
R
BI10
DI 5 ACT
This object indicates the status of Digital Input 5 .
ON/OFF
R
BI11
DI 6 ACT
This object indicates the status of Digital Input 6 .
ON/OFF
R
NOTE:
For Present Value Access Types, R = Read-only,
W = Writeable, C = Commandable . Commandable
values support priority arrays & relinquish defaults .
Binary Output Object Instance Summary
The following table summarizes the Binary Output Objects supported:
Table 38: Binary Output Objects
Instance ID
Object Name
Description
Active/ Inactive Text Present Value Access Type
BO0
RO1 COMMAND
This object controls the output state of Relay 1 . This control requires that
parameter 1401 value = COMM .
ON/OFF
C
BO1
RO2 COMMAND
This object controls the output state of Relay 2 . This control requires that
parameter 1402 value = COMM .
ON/OFF
C
BO2
RO3 COMMAND
This object controls the output state of Relay 3 . This control requires that
parameter 1403 value = COMM .
ON/OFF
C
BO3
RO4 COMMAND
This object controls the output state of Relay 4 . This control requires that
parameter 1410 value = COMM (also requires OREL-01 option) .
ON/OFF
C
BO4
RO5 COMMAND
This object controls the output state of Relay 5 . This control requires that
parameter 1411 value = COMM (also requires OREL-01 option) .
ON/OFF
C
BO5
RO6 COMMAND
This object controls the output state of Relay 6 . This control requires that
parameter 1412 value = COMM (also requires OREL-01 option) .
ON/OFF
C
NOTE:
For Present Value Access Types, R = Read-only,
W = Writeable, C = Commandable . Commandable
values support priority arrays & relinquish defaults .
e
Mbedded
f
ieldbUs
www .DaikinApplied .com 59
OM 1191 • MD5 VFD