WARNING
Relay coils generate noise spikes in response to steps in
applied power . To avoid drive damage from such spikes,
all AC relay coils mounted across drive inputs require R-C
snubbers, and all DC relay coils mounted across drive outputs
require diodes – see figure.
Analog Cables
Recommendations for analog signal runs:
• Use double shielded, twisted pair cable .
• Use one individually shielded pair for each signal .
• Do not use a common return for different analog signals .
Digital Cables
Recommendation for digital signal runs: A double shielded
cable is the best alternative, but single-shielded, twisted, multi-
pair cable is also usable .
Control Panel Cable
If the control panel is connected to the drive with a cable, use
only Category 5 Patch ethernet cable .
Drive’s Control Connection Terminals
The following table provides specifications for the drive’s
control terminals
Frame Size
Control
Maximum Wire Size
Torque
mm2
AWG
Nm
lb-ft
All
1 .5
16
0 .4
0 .3
Control Terminal Descriptions
The following full-page diagram provides a general description
of the control terminals on the drive. For specific application
details, see the
Application Macros on page 9
.
NOTE:
Terminals 3, 6, and 9 are at the same potential .
For safety reasons the fault relay signals a “fault”
when the MD5 is powered down .
T
eChniCal
d
aTa
www .DaikinApplied .com 85
OM 1191 • MD5 VFD