Group 36: Timed Functions
This group defines the timed functions. The timed functions include:
• Four daily start and stop times
• Four weekly start, stop and boost times
• Four timers for collecting selected periods together .
A timer can be connected to multiple time periods and a time period can be in multiple timers .
A parameter can be connected to only one timer . .
You can use the Timed functions assistant for easy configuring.
Table 19: Group 36: Timed Functions
Code Description
Range
Resolution
Default
S
3601 TIMERS ENABLE
-6…7
1
0 (NOT SEL)
Selects the source for the timer enable signal .
0 = NOT SEL – Timed functions are disabled .
1 = DI1 – Defines digital input DI1 as the timed function enable signal.
• The digital input must be activated to enable the timed function .
2…6 = DI2…DI6 – Defines digital input DI2…DI6 as the timed function enable signal.
7 = ACTIVE – Timed functions are enabled .
-1 = DI1(INV) – Defines an inverted digital input DI1 as the timed function enable signal.
• This digital input must be de-activated to enable the timed function .
• -2…-6 = DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the timed function enable signal.
3602 START TIME 1
00:00:00…23:59:58
2 s
12:00:00 AM
Defines the daily start time.
• The time can be changed in steps of 2 seconds .
• If parameter value is 07:00:00, the timer is activated at 7 a .m .
• The figure shows multiple timers on different weekdays.
OM 1191 • MD5 VFD 36 www .DaikinApplied .com