Table 5 continued: Group 01: Operating Data
0118 DI 1-3 STATUS
000…111
(0…7
decimal)
1
—
Status of the three digital inputs .
• Status is displayed as a binary number .
• 1 indicates that the input is activated .
• 0 indicates that the input is deactivated .
0119 DI 4-6 STATUS
000…111
(0…7
decimal)
1
—
Status of the three digital inputs .
• See parameter 0118 DI 1-3 STATUS .
0120 AI 1
0 .0…100 .0%
0 .1%
—
The relative value of analog input 1 in % .
0121 AI 2
0 .0…100 .0%
0 .1%
—
The relative value of analog input 2 in % .
0122 RO 1-3 STATUS
000…111
(0…7
decimal)
1
—
Status of the three relay outputs .
• 1 indicates that the relay is energized .
• 0 indicates that the relay is de-energized .
0123 RO 4-6 STATUS
000…111
(0…7
decimal)
1
—
Status of the three relay outputs . Available if OREL-01 Relay Output Extension Module is installed .
• See parameter 0122 .
0124 AO 1
0 .0…20 .0
mA
0 .1 mA
—
The analog output 1 value in milliamperes .
0125 AO 2
0 .0…20 .0
mA
0 .1 mA
—
The analog output 2 value in milliamperes .
0126 PID 1 OUTPUT
-1000 .0…
1000 .0%
0 .1%
—
The PID controller 1 output value in % .
0127 PID 2 OUTPUT
-100 .0…
100 .0%
0 .1%
—
The PID controller 2 output value in % .
0128 PID 1 SETPNT
Unit and
scale
defined
by par .
4006/4106
and
4007/4107
—
—
The PID 1 controller setpoint signal .
• Units and scale defined by PID parameters.
0129 PID 2 SETPNT
Unit and
scale
defined by
par . 4206
and 4207
—
—
The PID 2 controller setpoint signal .
• Units and scale defined by PID parameters.
0130 PID 1 FBK
Unit and
scale
defined
by par .
4006/4106
and
4007/4107
—
—
The PID 1 controller feedback signal .
• Units and scale defined by PID parameters.
OM 1191 • MD5 VFD 14 www .DaikinApplied .com