4. If the outdoor temperature decreases, the setpoint is lowered up to 68°F by the Sliding
Temperature function.
When the room temperature further decreases to 60°F, this function changes the
operation mode to Heat. At that time, the setpoint becomes 60°F. At the beginning,
heating was started with setpoint at 68°F, however, the setpoint became 60°F as a result
of the change heat
→
cool
→
heat.
2. When this function is simultaneously used with the schedule and interlocking control functions,
this function may not work as intended with the settings.
Example: When the method for referencing room temperature and setpoint is set up to Fixed and
the thermal difference to 7°F
1. Heating starts with setpoint for the indoor unit reference of indoor temperature and
setpoint set at 68°F.
2. The operation mode of that indoor unit is changed to Cool using the remote controller.
3. When the room temperature becomes 68°F or higher, the operation mode of the indoor
unit of the Auto Changeover group is changed to Cool and the setpoint set to 68°F. If the
operation mode had not been changed using the remote controller, the indoor unit works
in Heat mode until the room temperature becomes 75°F, and the setpoint should have
changed to 75°F when the operation mode changed to Cool but it didn’t.