User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
176
• Similarly, two analog values are compared as follows.
Success
Failure
Hysteresis
Hysteresis
Assessment interval (1 minute)
Assessment interval (1 minute)
Time
Analog value
Assessment
Offset
Offset
Analog value at management point (2)
Analog value at management point (2)
Management point (2) + Offset
Management point (2) + Offset
Example: [Analog value at the management point > Analog value at the management point + Offset ± Hysteresis]
Analog value at management point (1) >
Analog value at management point (2) + Hysteresis
Analog value at management point (1) <
Analog value at management point (2) + Offset – Hysteresis
Success
Failure
Except above
Not assessed (Previous assessment kept)
Analog value at management point (1)
Analog value at management point (1)
Success
Failure
Hysteresis
Hysteresis
Assessment interval (1 minute)
Assessment interval (1 minute)
Time
Time
Analog value
Assessment
Offset
Offset
Analog value at management point (2)
Analog value at management point (2)
Management point (2) + Offset
Management point (2) + Offset
Range condition can be defined by combining the two cases above.
Example: [
Analog value at the management point
<
Analog value at the management point
+ Offset ± Hysteresis]
Analog value at management point (1) <
Analog value at management point (2) + Offset – Hysteresis
Analog value at management point (1) >
Analog value at management point (2) + Hysteresis
Success
Failure
Except above
Not assessed (Previous assessment kept)
Analog value at management point (1)
Analog value at management point (1)