User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
258
Cautions when Using Simultaneously with Other Control Functions
1. Automatic control functions that work when there is no one in the room (such as Setback,
Temperature Limit, Pre-Cool/Pre-Heat) are exempt from the operation rules during their
operating hours.
2. Automatic control functions that work when there are people in the room (Auto Changeover,
HMO, Timer Extension, Sliding Temperature, Schedule, Interlocking Control) are subject to the
operation rules during their operating hours.
3. The operation rules do not apply to management points under maintenance.
•
Checking the Equipment Operational Status
Executes a sampling and displays management points operating out of the set up operation
rules. The checking results can also be output to a CSV file.
Selecting a sampling period, the sampling targets and applicable operation rules, and executing
a sampling displays a graph and a list.
Specify the sampling target by area. Sub areas and management points included in the area will
become targets.
There are two modes for displaying the sampling results: area sampling and management point
sampling.
In area sampling mode, results are sampled by area and only sub areas included in the selected
area are displayed.
In the management point sampling mode, the management points (including management points
of sub areas) included in the selected area are displayed.
The sampled information is presented in two tabs: Failure to turn off tab where management
points that were operating when they should be stopped are sampled, and Setpoint gap tab
where indoor units with gaps between the actual setpoint and the setpoint that should be set are
sampled.