User’s Manual EM11A017
DCM601A71 intelligent Touch Manager
169
•
Interlock Program Input Setup Screen
This screen is displayed when you touch the Modify button on the Interlock Program Setup
screen.
Sets up the inputs to the interlocking program.
(1)
(2)
(4)
(6)
(7)
(8)
(9)
(5)
(3)
(1)
Management Point Input
list
Displays a list of management points monitored as inputs to the interlocking program.
(2)
Timer (min.)
button
Displays the Numerical Input dialog that allows you to set the required duration.
The range of values you can enter is 0 to 30, in increments of 1. (1 to 30 for analog values)
(3)
Condition Setup
button
Displays the Condition Setup screen that allows you to set up the conditions required for the
management point selected in the Management Point Input list.
(4)
Available Management Points
list
Displays a list of management points that can be selected as input for the condition to detect
selected in the Detection Condition combo box.
(5)
Detection Condition
combo box
Selects the condition to detect at an available management point in the Available Management
Points list.
Select a condition to detect from: Switch, Equipment error, Analog upper limit error, Analog lower
limit error, Operation mode, and Analog value condition.
(6)
Add
button
Registers an available management point selected in the Available Management Points list to the
Management Point Input list.
You can register up to 50 management points to monitor. However, you cannot register areas.
(7)
Remove
button
Removes the management point selected in the Management Point Input list from monitoring.
(8)
OK
button
Saves the edit and closes the screen.
(9)
Cancel
button
Cancels the edit and closes the screen.