pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
The following parameters refer to line 2, for details, see the corresponding parameters for line 1 above
Cba01
DI
Alarm 1 compressor 1 DI position (line 2)
03
---
--- | 01…18
U1…U10 (****)
Status (display only)
Status Alarm 1 compressor 1 DI (line 2)
---
---
closed | open
Logic
Logic alarm 1 compressor 1 DI (line 2)
NC
---
NC | NO
Function (display only)
Alarm 1 compressor 1 function status (line 2)
---
---
not active | active
…
…
…
…
…
…
Cbb01
Regulation
Compressor control by temperature or pressure (line 2)
pressure
---
pressure
temperature
Reg. Type
Compressor regulation type (line 2)
dead zone
---
Proportion. band
dead zone
…
…
…
…
…
…
Cbc01
Compressor 1 operating
hours
Compressor 1 operating hours (line 2)
---
---
0…999999
…
…
…
…
…
…
Cbd01
Enable suction setpoint
compensation
Enable setpoint compensation (suction line 2)
NO
---
NO | YES
…
…
…
…
…
…
Cbe01
Number of alarms for each
compressor
Number of alarms for each compressor (line 2)
1
---
0…4
…
…
…
…
…
…
Cbf02
Compressor type
Type of compressors (line 2)
Recriproc.
---
Recriprocating
scroll
Number of compressors
Number of compressors (line 2)
2/3 (*)
---
1…12
…
…
…
…
…
…
Cbg01
Minimum voltage
Voltage corresponding to the minimum capacity of the inverter (line 2)
0.0
Hz
0.0…10.0
Maximum voltage
Voltage corresponding to the maximum capacity of the inverter (line 2)
10.0
Hz
0.0…10.0
Nominal freq.
Nominal frequency (frequency at nominal capacity) (line 2)
50
Hz
0…150
Nominal power
Nominal capacity for compressor managed by inverter at nominal frequency (line 2)
10.0
Kw
0.0…500.0
…
…
…
…
…
…
Cca02
RPRV opening
Flash gas valve opening percentage to enable parallel line activation
30
%
0…100
Delay
Evaluation time for activation of parallel line from when reaching the set fl ash valve
opening
10
s
…
Min g.c. temp
Activation threshold relative to gas cooler outlet temperature
25°C
°C/°F
…
Tgc off thr
Parallel compression or parallel compressor line deactivation threshold relative to gas cooler
outlet temperature
15°C
°C/°F
…
Cca03
RPRV off set with par. comp.
on
Off set applied to receiver pressure set point when at least one parallel compressor is active 2.0 barg
barg/psig
…
Par. Comp. ON rising time
RPRV
Time needed to add the off set to the receiver pressure set point
0
s
…
Par. Comp. OFF falling time
RPRV
Time needed to subtract the off set from the receiver pressure set point
20
s
…
Cca04
Setpoint
Set point for proportional control of integrated parallel compressor on the main board
35 barg
barg/psig
Prop gain
Proportional gain for proportional control of integrated parallel compressor on the main
board
10
%
0…100
Ti
Integral time for proportional control of integrated parallel compressor on the main board
30
s
…
Td
Derivative time for proportional control of integrated parallel compressor on the main
board
0
s
…
Cca05
Min.time on
Minimum integrated parallel compressor ON time
30
s
0…999
Min.time off
Minimum integrated parallel compressor OFF time
120
s
0…999
Min.time on
same compr.
Minimum time between starts of same integrated parallel compressor
360
s
0…999
Cca06
Minimum voltage
Voltage corresponding to minimum power of the integrated parallel compressor inverter
0.0
V
0.0…10.0
Maximum voltage
Voltage corresponding to maximum power of the integrated parallel compressor inverter
10.0
V
0.0…10.0
Nominal freq.
Minimum integrated parallel compressor inverter frequency
30
Hz
0…150
Nominal power
Maximum integrated parallel compressor inverter frequency
60
Hz
0…150
Cca07
Nominal freq.
Nominal frequency (frequency at nominal power) of the integrated parallel compressor
50
Hz
0…150
Rising time
Time to move from integrated parallel compressor modulating device minimum to
maximum power
20
s 0…600
Falling time
Time to move from integrated parallel compressor modulating device maximum to
minimum power
20
s 0…600
Cca11
Delay
Integrated parallel compressor generic alarm activation delay
0
s
0…999
Delay at start
Integrated parallel compressor generic alarm activation delay at start-up
0
s
0…999
Reset
Type of integrated parallel compressor generic alarm reset
automatic
…
automatic
manual
Priority
light
…
light | serious
Cca12
DI
Integrated parallel compressor generic alarm DI input position
---
---
01…18, U1…U10
Status
Integrated parallel compressor generic alarm DI status
---
---
closed | open
Logic
Integrated parallel compressor generic alarm DI logic
NC
---
NC | NO
Function
Integrated parallel compressor generic alarm function status
---
---
not active | active
Eia14
Comp. Par. disch. Temp
Integrated parallel compressor discharge temperature
---
---
U1…U10
Cca08
Threshold
High discharge temperature alarm activation threshold for the integrated parallel
compressor
120°C
°C/°F
---
Diff erent.
High discharge temperature alarm activation diff erential for the integrated parallel
compressor
5°C
°C/°F
---
Delay
High discharge temperature alarm activation delay for the integrated parallel compressor
5
s
---
Cca13
DO relay line
DO position and display status (ON/OFF) for integrated parallel compressor
---
---
DO1…DO18
Logic
DO logic of integrated parallel compressor power supply
NC
---
NC | NO
Cca14
AO
Integrated parallel compressor modulating device AO position
---
---
01…06
Status (display only)
Integrated parallel compressor modulating device AO value
0.0
%
0…100.0
Tab. 7.d
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
D.Condensers
The I/Os depend on the confi guration selected, the following are only examples. See Appendix A.1 for the complete list and position of available I/Os.
Daa01
DI
Fan 1 overload DI position (line 1)
…
---
---, 01…18,
U1…U10 (****)
Status (display only)
Fan 1 overload DI status (line 1)
---
---
closed | open
Logic
Fan 1 overload DI logic (line 1)
NC
---
NC | NO
Function (display only)
Fan 1 overload function status (line 1)
---
---
not active | active
…
…
…
…
…
…
Page 111 of 172
Copyright HPL March 2021
P4114S Rev 03
Содержание Hubbard GCU2040PXB1
Страница 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 44: ...4 Wiring Schematics Model GCU2040PXB1 Part Number D4155S Page 44 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 161: ...8 PRESSURE ENTHALPY DIAGRAM FOR R744 REFRIGERANT Page 161 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...