pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
Aaan (display
only)
Reg.var.
Value of the regulation variable for the generic function in stage 1
---
… …(**)
Enable
Status of the enabling variable for the generic function in stage 1
---
---
Not active | Active
Setpoint
Regulation setpoint for the generic function in stage 1
---
…
…(**)
Diff eren.
Regulation diff erential for the generic function in stage 1
---
…
…(**)
Mode
Regulation mode for the generic function in stage 1 (direct or reverse)
---
---
D, R
Status
Status of the generic function in stage 1
---
---
Not active | Active
…
…
…
…
…
…
Aaar (display
only)
Reg.var.
Value of the regulation variable for the generic function in stage 5
---
…
…(**)
Enable
Status of the enabling variable for the generic function in stage 5
---
---
Not active | Active
Setpoint
Regulation setpoint for the generic function in stage 5
---
…
…(**)
Diff eren.
Regulation diff erential for the generic function in stage 5
---
…
…(**)
Mode
Regulation mode for the generic function in stage 5 (direct or reverse)
---
---
D, R
Status
Status of the generic function in stage 5
---
---
Not active | Active
Aaas (display
only)
Reg.variab.
Value of the regulation variable for generic modulating function 1
---
…
…(**)
Enable
Status of the enabling variable for generic modulating function 1
---
---
Not active | Active
Setpoint
Regulation setpoint for generic modulating function 1
---
…
…(**)
Diff eren.
Regulation diff erential for generic modulating function 1
---
…
…(**)
Mode
Regulation mode for generic modulating function 1 (direct or reverse)
---
---
D, R
Status
Status of generic modulating function 1
---
%
0.0…100.0
Aaat (display
only)
Reg.variab.
Value of the regulation variable for generic modulating function 2
---
…
…(**)
Enable
Status of the enabling variable for generic modulating function 2
---
---
Not active | Active
Setpoint
Regulation setpoint for generic modulating function 2
---
…
…(**)
Diff eren.
Regulation diff erential for generic modulating function 2
---
…
…(**)
Mode
Regulation mode for generic modulating function 2 (direct or reverse)
---
---
D, R
Status
Status of generic modulating function 2
---
%
0.0…100.0
Aaau (display
only)
Reg.variab.
Value of the regulation variable for generic alarm function 1
---
---
Not active | Active
Enable
Status of the enabling variable for generic alarm function 1
---
---
Not active | Active
Type
Type of alarm for generic alarm function 1
---
---
Normal | Serious
Delay
Regulation diff erential for generic alarm function 1
---
s
0…9999
Status
Status of generic alarm function 1
---
---
Not active | Active
Aaav (display
only)
Reg.variab.
Value of the regulation variable for generic alarm function 2
---
---
Not active | Active
Enable
Status of the enabling variable for generic alarm function 2
---
---
Not active | Active
Type
Type of alarm for generic alarm function 2
---
---
Normal | Serious
Delay
Regulation diff erential for generic alarm function 2
---
s
0…9999
Status
Status of generic alarm function 2
---
---
Not active | Active
Aaaw (display
only)
Day
Day of the week
---
---
Monday, ..., Sunday
F1: --:-- -> --:--
Enabling and defi nition of time band 1: start hour and minute, end hour and minute for the
generic scheduling function
---
…
…
…
…
…
…
…
F4: --:-- -> --:--
Enabling and defi nition of time band 4: start hour and minute, end hour and minute for the
generic scheduling function
---
…
…
Status
Status of the general scheduling function
---
---
Not active | Active
Aaax (display
only)
HR 1 Request:
Percentage of fi rst heat reclaim request
%
HR 1 Status:
Status of fi rst heat reclaim request
ON | OFF
Water temp.:
Water temperature with HR1 regulated by temperature
°C/°F
Valve:
Status of fi rst heat reclaim valve
Open | Closed
Pump:
Status of fi rst heat reclaim pump
ON | OFF
Pump An. Out:
Running percentage of fi rst heat reclaim pump
%
Aaay (display
only)
HR 2 Request:
Percentage of second heat reclaim request
%
HR 2 Status:
Status of second heat reclaim request
ON | OFF
Water temp.:
Water temperature with HR2 regulated by temperature
°C/°F
Valve:
Status of second heat reclaim valve
Open | Closed
Pump:
Status of second heat reclaim pump
ON | OFF
Pump An. Out:
Running Percentage of second heat reclaim pump
%
Aaaz (display
only)
Status
Status of the ChillBooster device (line 1)
---
---
ON | OFF
Ext.Temp.
External temperature (line 1)
---
…
…(**)
Thresh.est.t.
Threshold for activating the ChillBooster device (line 1)
---
…
…(**)
F.Time100%
Number of minutes passed with fan at 100/number of minutes allowed (line 1)
---
min
0…999 | 0…999
Aaba (display
only)
Status
Status of the ChillBooster device (line 2)
---
---
ON | OFF
Ext.Temp.
External temperature (line 2)
---
…
…(**)
Thresh.est.t.
Threshold for activating the ChillBooster device (line 2)
---
…
…(**)
F.Time100%
Number of minutes passed with fan at 100/number of minutes allowed (line 2)
---
min
0…999 | 0…999
Aabb (display
only)
Cond.Temp.
Condensing saturated temperature (line 1)
---
…
…(**)
LiquidTemp
Liquid temperature (line 1)
---
…
…(**)
Subcool
Subcooling (line 1)
---
…
…(**)
Status
Status of the subcooling function (line 1)
---
---
Open | Closed
Aabc (display
only)
Cond.Temp.
Condensing saturated temperature (line 2)
---
…
…(**)
LiquidTemp
Liquid temperature (line 2)
---
…
…(**)
Subcool
Subcooling (line 2)
---
…
…(**)
Status
Status of the subcooling function (line 2)
---
---
Open | Closed
Ab01 (display
only)
UserSetp.
Setpoint set by the user for suction regulation under pressure, proportional regulation
(line 1)
---
… …(**)
ActualSetp.
Actual setpoint for suction regulation under pressure, proportional regulation (with
compensations applied, line 1)
---
… …(**)
Diff .
Suction regulation under pressure diff erential, proportional regulation (line 1)
---
…
…(**)
Ab02 (display
only)
UserSetp.
Setpoint set by the user for suction regulation under pressure, proportional regulation
(line 1)
---
… …(**)
ActualSetp.
Actual setpoint for suction regulation under pressure, proportional regulation (with
compensations applied, line 1)
---
… …(**)
Dead zone
Dead zone for suction regulation under pressure (line 1)
---
…
…(**)
Incr.Diff .
Increase diff erential for suction regulation under pressure, regulation in dead zone (line 1)
---
…
…(**)
Decr.Diff .
Decrease diff erential for suction regulation under pressure, regulation in dead zone (line 1)
---
…
…(**)
Ab03 (display
only)
UserSetp.
Setpoint set by the user for suction regulation under pressure, proportional regulation
(line 2)
---
… …(**)
ActualSetp.
Actual setpoint for suction regulation under pressure, proportional regulation (with
compensations applied, line 2)
---
… …(**)
Diff .
Suction regulation under pressure diff erential, proportional regulation (line 2)
---
…
…(**)
Ab04 (display
only)
UserSetp.
Setpoint set by the user for suction regulation under pressure, proportional regulation
(line 2)
---
… …(**)
ActualSetp.
Actual setpoint for suction regulation under pressure, proportional regulation (with
compensations applied, line 2)
---
… …(**)
Dead zone
Dead zone for suction regulation under pressure (line 2)
---
…
…(**)
Incr.Diff .
Increase diff erential for suction regulation under pressure, regulation in dead zone (line 2)
---
…
…(**)
Decr.Diff .
Decrease diff erential for suction regulation under pressure, regulation in dead zone (line 2)
---
…
…(**)
Page 105 of 172
Copyright HPL March 2021
P4114S Rev 03
Содержание Hubbard GCU2040PXB1
Страница 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 44: ...4 Wiring Schematics Model GCU2040PXB1 Part Number D4155S Page 44 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 161: ...8 PRESSURE ENTHALPY DIAGRAM FOR R744 REFRIGERANT Page 161 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...