58
ENG
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
Bab65
---
Common oil receiver pressure probe position (line 2)
---
---
U1…U10 (****)
---
Common oil receiver pressure probe type (line 2)
4...20mA
---
----, 0-1V
0-10V
4...20mA
0-5V
--- (display only)
Common oil receiver pressure value (line 2)
---
…
…(**)
Max limit
Maximum common oil receiver pressure value (line 2)
44.8 barg
…
…(**)
Min limit
Minimum common oil receiver pressure value (line 2)
0.0 barg
…
…(**)
Calibrat.
Common oil receiver pressure probe calibration (line 2)
0.0 barg
…
…(**)
Bab75
---
Discharge pressure probe position (line 1)
---
---
U1…U10 (****)
---
Discharge pressure probe type (line 1)
4...20mA
---
----, 0-1V
0-10V
4...20mA
0-5V
--- (display only)
Discharge pressure value (line 1)
---
…
…(**)
Max limit
Maximum discharge pressure value (line 1)
44.8 barg
…
…(**)
Min limit
Minimum discharge pressure value (line 1)
0.0 barg
…
…(**)
Calibrat.
Discharge pressure probe calibration (line 1)
0.0 barg
…
…(**)
…
…
…
…
…
…
Bac02
Line relay DO
Compressor 1 line relay DO position and status (On/Off ) display (line 1)
…
---
--- | 01…18 (****)
Part winding DO/Star relay
DO (*)
Compressor 1 part winding or star DO position and status (On/Off ) display (line 1)
…
---
--- | 01…18 (****)
---/Delta relay DO (*)
Compressor 1 delta DO position and status (On/Off ) display (line 1)
…
---
---, 01…18 (****)
Logic
Logic for compressor 1 power supply DO (line 1)
NO
---
NC | NO
Bac03
DO
Compressor 1 unloader 1 DO position (line 1)
…
---
---, 01…18 (****)
Status (display only)
Status for compressor 1 unloader 1 DO (line 1)
---
---
Closed | Open
Logic
Logic for compressor 1 unloader 1 DO (line 1)
NO
---
NC | NO
Function (display only)
Compressor 1 unloader 1 function status (line 1)
---
---
Not active | Active
…
…
…
…
…
…
Bac71
DO
Solenoid valve DO position for managing common oil diff erential
---
---
---, 01…18 (****)
Status (display only)
Solenoid valve DO status for managing common oil diff erential
---
---
Closed | Open
Logic
Solenoid valve DO logic for managing common oil diff erential
NC
---
NC | NO
Function
Status of the solenoid valve for managing common oil diff erential
---
---
Not active | Active
Bacef
DO Line relay
DO position and On/Off Status Parallel compressor consent
…
…
---, 01…18 (****)
Logic:
Logic Parallel compressor consent DO:
NA
…
NC | NA
…
…
…
…
…
…
Bad01
AO
Compressor modulating device AO position (line 1)
0
---
---, 01…06 (****)
Status (display only)
Modulating device output value (line 1)
0
%
0.0…100.0
…
…
…
…
…
…
Bb01
Suction L1
Suction line 1 in manual mode
Disabled
---
Disabled | abled
Suction L2
Suction line 2 in manual mode
Disabled
---
Disabled | abled
Condenser L1
Condenser line 1 in manual mode
Disabled
---
Disabled | abled
Condenser L2
Condenser line 2 in manual mode
Disabled
---
Disabled | abled
Timeout
Manual mode duration after last key pressed
10
min
0…500
Bba02
Compressor 1
Force to
Manual stages request for compressor 1 (line 1)
OFF
---
OFF | ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
…
…
…
…
…
…
Bba16
Compressor 12
Force to
Manual stages request for compressor 12 (line 1)
OFF
---
OFF | ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
Bba17
Oil Cool. pump 1
Force to
Manual operation status for oil cooling pump 1 (line 1)
OFF
---
OFF | ON
Oil cool pump 2
Force to
Manual operation status for oil cooling pump 2 (line 1)
OFF
---
OFF | ON
Bba18
Oil cool fan 1
Force to
Manual operation status for oil cooling fan 1 (line 1)
OFF
---
OFF | ON
Bba20
Compressor 1
Force to
Manual stages request for compressor 1 (line 2)
OFF
---
OFF | ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
…
…
…
…
…
…
Bba34
Compressor 12
Force to
Manual stages request for compressor 12 (line 2)
OFF
---
OFF | ON
2 STAGES (*)
3 STAGES (*)
4 STAGES (*)
Bba35
Oil Cool. pump 1
Force to
Manual operation status for oil cooling pump 1 (line 2)
OFF
---
OFF | ON
Oil Cool. pump 2
Force to
Manual operation status for oil cooling pump 2 (line 2)
OFF
---
OFF | ON
Bba37
Oil cool fan 1
Force to
Manual operation status for oil cooling fan (line 2)
OFF
---
OFF | ON
Bba38
Fan 1
Force to
Manual operation status for fan 1 (line 1)
OFF
---
OFF | ON
…
…
…
…
…
…
Bba53
Fan 16
Force to
Manual operation status for fan 16 (line 1)
OFF
---
OFF | ON
Bba54
Heat rec.pump
Force to
Manual operation status for heat recovery pump (line 1)
OFF
---
OFF | ON
Bba55
ChillBooster
Force to
Manual operation status for ChillBooster (line 1)
OFF
---
OFF | ON
Bba57
Fan 1
Force to
Manual operation status for fan 1 (line 2)
OFF
---
OFF | ON
…
…
…
…
…
…
Bba72
Fan 16
Force to
Manual operation status for fan 16 (line 2)
OFF
---
OFF | ON
Bba73
Heat rec.pump
Force to
Manual operation status for heat recovery pump (line 2)
OFF
---
OFF | ON
Bba74
ChillBooster
Force to
Manual operation status for ChillBooster (line 2)
OFF
---
OFF | ON
Bbb05
Compressor 1
Force to
Manual request for continuous capacity for compressor 1 (line 1)
0.0
%
0.0…100.0
Page 107 of 172
Copyright HPL March 2021
P4114S Rev 03
Содержание Hubbard GCU2040PXB1
Страница 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 44: ...4 Wiring Schematics Model GCU2040PXB1 Part Number D4155S Page 44 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 161: ...8 PRESSURE ENTHALPY DIAGRAM FOR R744 REFRIGERANT Page 161 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...