55
ENG
pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
Aa34 (display
only)
C01, C02, …C12
Time remaining for next compressor startup (line 2)
---
s
0…32000
C01
Power delivered from compressor 1 from line 2 (a "!" to the right of the value means that
some form of compressor power forcing is active, e.g., safety times, alarms, startup procedure)
---
%
0…100
…
…
…
…
…
C12
Power delivered from compressor 12 (line 2)
---
%
0…100
Aa35 (display
only)
Temperature
Suction temperature (line 2)
---
…
…(**)
Superheat.
Superheating (line 2)
---
…
…(**)
Aa41 (display
only)
Disch. 1
Discharge temperature compressor 1 (line 2)
---
…
…(**)
…
…
…
…
…
Disch. 6
Discharge temperature compressor 6 (line 2)
---
…
…(**)
Aa43 (display
only)
In.liq.1: DO
Digital output number associated and liquid injection status compressor 1 (line 2)
---
…
0…29 | ON | OFF
…
…
…
…
…
In.liq.6: DO
Digital output number associated and liquid injection status compressor 6 (line 2)
---
…
0…29 | ON | OFF
Aa45 (display
only)
Discharge temperature
Discharge temperature Digital Scroll
TM
compressor (line 2)
---
…
…(**)
Cap.Reduction
Capacity reduction Digital Scroll
TM
compressor (line 2) in progress
NO | YES
Oil sump T.
Oil sump temperature Digital Scroll
TM
compressor (line 2)
---
…
…(**)
Oil status
Oil dilution status Digital Scroll
TM
compressor (line 2)
Ok | Diluted
Aa46 (display
only)
Status
Operational status Digital Scroll
TM
compressor (line 2)
---
---
OFF
start
ON
Alarm
OFF for time
ON for time
manual mode
in pump down
Count
Safety time count Digital Scroll
TM
compressor (line 2)
---
s
0…999
Compr.
Status Digital Scroll
TM
compressor (line 2)
---
---
ON | OFF
Valve
Status Digital Scroll
TM
valve (line 2)
---
---
ON | OFF
Cap.Req.
Capacity requested Digital Scroll
TM
compressor (line 2)
---
%
0…100
ActualCapac.
Actual capacity Digital Scroll
TM
compressor (line 2)
---
%
0…100
Aa50 (display
only)
Pressure
Condensing pressure (line 2)
---
…
…(**)
Sat.Temp.
Condensing saturated temperature (line 2)
---
…
…(**)
ActualSet
Actual setpoint for pressure regulation (with compensations applied, line 2)
---
…
…(**)
Diff eren.
Regulation diff erential for pressure regulation (line 2)
---
…
…(**)
Aa51 (display
only)
Pressure
Condensing pressure (line 2)
---
…
…(**)
Sat.Temp.
Condensing saturated temperature (line 2)
---
…
…(**)
ActualSet
Actual setpoint for temperature regulation (with compensations applied, line 2)
---
…
…(**)
Diff eren.
Regulation diff erential for temperature regulation (line 2)
---
…
…(**)
Aa52 (display
only)
Act/Req.
Power delivered/Power requested per condensing line (line 2)
---
%
0 | 0 …100 | 100
Reg. Status
Regulation status (according to the type of regulation set, line 2)
---
---
stop
increase
decrease
stand-by
functioning
timings
alarms
Reg. Type
Condenser regulation Type (line 2)
---
---
Proportional Band
Dead zone
Setpoint
Actual condensing setpoint (with compensations applied, line 2)
---
…
…(**)
Aa53 (display
only)
F1
Power delivered from fan 1 of line 2 (a "!" to the right of the value means that some form of
power forcing is active)
---
%
0…100
…
…
…
…
…
F8
Power delivered from fan 8 of line 2 (a "!" to the right of the value means that some form of
power forcing is active)
---
%
0…100
Aa54 (display
only)
F9
Power delivered from fan 9 of line 2 (a "!" to the right of the value means that some form of
power forcing is active)
---
%
0…100
…
…
…
…
…
F16
Power delivered from fan 16 of line 2 (a "!" to the right of the value means that some form of
power forcing is active)
---
%
0…100
Aa55 (display
only)
Discharge temperature
Discharge temperature (line 2)
---
…
…(**)
External temperature
External temperature (line 2)
---
…
…(**)
Aa61
(display only)
Suct Press
Suction pressure value in the medium temperature compressor line
---
…
…(**)
Oil Press
Oil receiver pressure value
---
…
…(**)
Delta
Diff erence between receiver oil pressure and suction pressure (medium temperature
compressors or liquid receiver when integrated parallel compressor activated or in pLAN
when using the same I/Os)
--- …
…(**)
Actual Setp
Pressure diff erential set point (receiver - suction)
1.0
barg/psig …
Diff erential
Return diff erential for deactivation of the oil diff erential function
0.5
barg/psig …
State
Oil diff erential function status (YES
Æ
ACTIVE, NO
Æ
INACTIVE)
NO
---
YES | NO
Aa65
S1 probe
Driver pressure probe S1 (driver connected in Fieldbus)
---
bar
-290…2900
S2 probe
Driver pressure probe S2 (driver connected in Fieldbus)
---
°C
-870…2900
S3 probe
Driver pressure probe S3 (driver connected in Fieldbus)
---
bar
-290…2900
S4 probe
Driver pressure probe S4 (driver connected in Fieldbus)
---
°C
-870…2900
Aa66
Digital input staus 1
Driver digital input 1 (driver connected in Fieldbus)
---
---
Open | Closed
Digital input staus 2
Driver digital input 2 (driver connected in Fieldbus)
---
---
Open | Closed
Aa77 (display
only)
Parallel compressor status:
Parallel compressor status
ON/OFF
ON | OFF |
not active
GC out.temp.:
Gas Cooler Outlet temperature
°C/°F
RPRV opening:
RPRV valve opening
%
RPRV setp.:
RPRV Setpoint
barg
Aaa76 (display
only)
HR Total Request:
Percentage of heat reclaim used to activate diff erent actions. It can refer to HR1 or HR2 or
HR1+HR2
%
Status:
Detailed description of current running action
Run actions:
Run actions presence
YES | No
Min HPV set.:
Current minimum HPV setpoint 40
barg
Off set GC:
Current temperature GC off set (to increase GC setpoint)
°C/°F
HR prevent:
HR confi gured as prevent and active
ON | OFF
Aaa77 (display
only)
HR Total Request:
Percentage of heat reclaim used to activate diff erent actions. It can refer to HR1 or HR2 or
HR1+HR2
%
Bypass Allowed
Status of bypass allowed
GC out. Temp:
Current GC out temperature
°C/°F
GC byp. Temp:
Current GC baypassed temperature
°C/°F
GC reg. temp:
Current regulation temperature: Tgc out if bypass off , Tgc byp if bypass on
°C/°F
Gas Cooler byp:
Opening percentage of bypass valve
%
Page 104 of 172
Copyright HPL March 2021
P4114S Rev 03
Содержание Hubbard GCU2040PXB1
Страница 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 44: ...4 Wiring Schematics Model GCU2040PXB1 Part Number D4155S Page 44 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 161: ...8 PRESSURE ENTHALPY DIAGRAM FOR R744 REFRIGERANT Page 161 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...