pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
Efb09
High alarm
High alarm enabling for generic modulating function 1
disable
---
disable | enable
High alarm
High alarm threshold for generic modulating function 1
0.0 °C
…
… (**)
Delay
High alarm delay for generic modulating function 1
0
s
0…9999
Alarm type
Low alarm type for generic modulating function 1
Normal
---
Normal | Serious
Efb20
Low alarm
Low alarm enabling for stage 1 generic function
Disable
---
disable | Enable
Low alarm
Low alarm threshold for stage 1 generic function
0.0 °C
…
… (**)
Delay
Low alarm delay for stage 1 generic function
0
s
0…9999
Alarm type
Low alarm type for stage 1 generic function
Normal
---
Normal | Serious
Efb10
Out upper limit
Output upper limit for generic modulating function 1
100.0
%
0…100
Out lower limit
Output lower limit for generic modulating function 1
0.0
%
0…100
Cut-off enable
Enable cut-off function for generic modulating function 1
NO
---
NO | YES
Cutoff Diff Cut-off diff erential for generic modulating function 1
0.0 °C
…
… (**)
Cutoff hys.
Cut-off hysteresis for generic modulating function 1
0.0 °C
…
… (**)
…
…
…
…
…
…
Efb15
Out upper limit
Output upper limit for generic modulating function 1
100.0
%
0…100
Out lower limit
Output lower limit for generic modulating function 1
0.0
%
0…100
Cut-off enable
Enable cut-off function for generic modulating function 1
NO
---
NO | YES
Cutoff Diff Cut-off diff erential for generic modulating function 1
0.0 °C
…
… (**)
Cutoff hys.
Cut-off hysteresis for generic modulating function 1
0.0 °C
…
… (**)
…
…
…
…
…
…
Efc05
JAN Alarm 1
Enable generic alarm function 1
disable
---
disable | Enable
JAN Alarm 2
Enable generic alarm function 2
disable
---
disable | Enable
Efc06
Regulation variable
Monitored variable for generic alarm function 1
---
---
…
Enable
Enabling variable for generic alarm function 1
---
---
…
Description
Enable description change
Salta
---
Skip | Change
---------------
Description
---
---
…
Efc07
Alarm type
Priority type for generic alarm function 1
Normal
---
Normal | Serious
Delay
Delay for generic alarm function 1
0
s
0…9999
…
…
…
…
…
…
Efd05
Enable generic
scheduler funct.
Enable generic scheduler function
disable
---
disable | enable
JAN. scheduling connected
to common scheduler
Generic scheduler with the same days and special periods
NO
---
NO | YES
Efd06
Enable
Enabling variable for generic scheduler function
---
---
…
Efd07
TB1: --:-- -> --:--
Enabling and defi nition of time band 1: start hour and minute, end hour and minute
(suction line 1)
---
…
…
…
…
…
…
…
TB4: --:-- -> --:--
Enabling and defi nition of time band 4: start hour and minute, end hour and minute
(suction line 1)
---
…
…
Change
Time band change action
---
---
---
save changes
load previous
clear all
Copy to
Copy settings to other days
0
---
MONDAY...SUNDAY;
MON-FRI; MON-SAT;
SAT&SUN; ALL
Efe05
JAN. A measure
Generic analog input A unit of measure selection
°C
---
°C | °F | barg |
psig | % | ppm
…
…
…
…
…
Efe06/Efe07 (**)
---
Generic probe A position
B1
---
---, U1…U10 (****)
---
Generic probe A type
4...20 mA
---
…(**)
--- (display only)
Generic probe A value
---
…
…(**)
Max limit
Generic probe A maximum limit
30.0 barg
…
…(**)
Min limit
Generic probe A minimum limit
0.0 barg
…
…(**)
Calibration
Generic probe A calibration
0.0 barg
…
…(**)
…
...
...
…
…
…
Efe21
DO
Generic stage 1 DO position
…
---
---, 01…18 (****)
Status (display only)
Status of generic stage 1 DO
---
---
closed | open
Logic
Logic of generic stage 1 DO
NO
---
NC | NO
Function (display only)
Generic stage 1 function status
---
---
not active | active
…
…
…
…
…
…
Efe29
Modulating1
Generic modulating 1 AO position
0
---
---, 01…06 (****)
Status (display only)
Generic modulating 1 function output value
0
%
0.0…100.0
…
…
…
…
…
…
Egaa01
DI
ChillBooster fault DI position (line 1)
---
---
---, 01…18, U1…
U10 (****)
Status
ChillBooster fault DI status (line 1)
---
---
closed | open
Logic
ChillBooster fault DI logic (line 1)
NC
---
NC | NO
Function
ChillBooster fault function status (line 1)
---
---
not active | active
Egaa02
DO
ChillBooster fault DO position (line 1)
…
---
---, 01…18 (****)
Status (display only)
ChillBooster fault DO status (line 1)
---
---
closed | open
Logic
ChillBooster fault DO logic (line 1)
NO
---
NC | NO
Function (display only)
ChillBooster function status (line 1)
---
---
not active | active
Egab01
Device present
Enable ChillBooster function (line 1)
NO
---
NO | YES
Deactivation when
fan power less than
Fan capacity under which the ChillBooster is deactivated (line 1)
95
%
0…100
Egab02
Before activ. fans at
max for
Min. time for fans at maximum capacity before ChillBooster activation (line 1)
5
min
0…300
Ext.tempThresh
External temperature threshold for ChillBooster activation (line 1)
30.0 °C
…
…(**)
Egab03
Sanitary proc.
Enable sanitary procedure (line 1)
Disable
---
disable | Enable
Start
Sanitary procedure starting time (line 1)
00:00
---
…
Duration
Sanitary procedure duration (line 1)
0
min
0…30
Ext.tempThresh
External temperature threshold for sanitary procedure activation (line 1)
5.0 °C
…
…(**)
Egab04
Maint. req. Chillb. after
Tempo massimo funzionamento ChillBooster (linea 1)
200
h
0…999
Maint time reset
Reset tempo funzionamento ChilllBooster (linea 1)
NO
---
NO | YES
Ehb01
Avoid simultaneous pulse
between lines
Abilitazione inibizione spunti contemporanei compressori
NO
---
NO | YES
Delay
Ritardo tra partenze compressori linee diverse
0
s
0…999
Ehb03
Force3 off L2 comps
for L1 fault
Abilitazione forzatura OFF compressori linea 2 per guasto compressori linea 1
NO
---
NO | YES
Delay
Ritardo forzatura OFF compressori linea 2 per guasto compressori linea 1
0
s
0…999
Ehb04
Activ. L1 comps for
L2 activ.
Abilitazione forzatura ON compressori linea 1 per accensione compres. linea 2
NO
---
NO | YES
Delay
Ritardo forzatura ON compressori linea 1 per accensione compressori linea 2
30
s
0…999
Force off L2 comps for L1 off Abilitazione forzatura OFF compressori linea 2 per off linea 1
NO
---
NO | YES
Ehb05
Enable minimum threshold
for act. of L1
Enable line 1 activation for DSS only when the suction pressure is greater than a minimum
threshold
NO
---
NO | YES
Threshold
Minimum threshold for line 1 activation for DSS
---
…
… (**)
Page 117 of 172
Copyright HPL March 2021
P4114S Rev 03
Содержание Hubbard GCU2040PXB1
Страница 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 44: ...4 Wiring Schematics Model GCU2040PXB1 Part Number D4155S Page 44 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 161: ...8 PRESSURE ENTHALPY DIAGRAM FOR R744 REFRIGERANT Page 161 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...