pRack PR300T +0300018EN rel. 1.5 - 02.05.2017
Mask index
Display description
Description
Def
.
U
.
of M
.
V
alues
Caf04
Refrigerant type
Type of refrigerant (suction line 1)
R744
---
R22 | R134a
R404A | R407C
R410A | R507A
R290 | R600
R600a | R717
R744 | R728
R1270 | R417A
R422D | R413A
R422A | R423A
R407A | R427A
R245Fa | R407F | R32
Caf05
Min.time on
Minimum compressor on time (line 1)
30
s
0…999
Min.time off
Minimum compressor off time (line 1)
120
s
0…999
Minimum time to start same
comp.
Minimum time between starts of same compressor (line 1)
360
s
0…999
Caf06
Startup
Type of compressor startup
direct
---
Direct
Part winding
Star delta
Caf07
Star time
Star relay run time
0
ms
0…9999
Star delay/line
Delaty betwen star and line relay
0
ms
0…9999
Star delta delay
Delay between star and delta relay
0
ms
0…9999
Caf08
Partwinding delay
Partwinding delay
0
ms
0…9999
Caf09
Equalization
Enable compressor equalization at startup
NO
---
NO | YES
Equal. time
Equalization duration
0
s
0…999
Caf10
Device rotation type
Type of rotation
FIFO
---
---
FIFO
LIFO
TIME
CUSTOM
Caf11
Device sequence
Unloader sequence in relation to compressor activation (C=compressor, P=unloader)
CpppCppp ---
----
CCpppppp
CpppCppp
Caf12
Load up time
Delay between diff erent compressor starts
10
s
0…999
Shutdown time
Delay between diff erent compressor shutdowns
0
s
0…999
Unloader delay
Delay between stages
0
s
0…999
Caf13
Custom rotation on order
Order of startup for compressor custom rotation
1
---
1…16
Caf14
Custom rotation off
Order of shutdown for compressor custom rotation
1
---
1…16
Caf15
Modulation device
Compressor modulating device type (line 1)
None
---
None
Inverter
Digital scroll
Caf16
Min frequency
Minimum inverter frequency
30
Hz
0…150
Max frequency
Maximum inverter frequency
60
Hz
0…150
Caf17
Min.time on
Minimum time compressor controlled by inverter on (line 1)
30
s
0…999
Min.time off
Minimum time compressor controlled by inverter off (line 1)
60
s
0…999
Minimum time to start same
comp.
Minimum time compressor controlled by inverter startup (line 1)
180
s
0…999
Caf18
Digital comp. valve
regulation
Digital Scroll™ compressor valve control type (line 1)
Optimized
regulation
---
Optimized regulat.
Variable cycle time
Fixed cycle time
Cycle time
Cycle time (line 1)
13
s
12…20
Caf19
Oil dilution
Enable Digital Scroll™ oil temperature alarm (line 1)
enable
---
disable | enable
Discharge temp
Enable Digital Scroll™ discharge temperature alarm (line 1)
enable
---
disable | enable
…
…
…
…
…
…
Caf90
Diff erent sizes
Enable compressors of diff erent sizes (line 1)
NO
---
NO | YES
Diff erent number of valves
Enable compressor partialization (line 1)
NO
---
NO | YES
Caf91
S1
Enable size and size for compressor group 1 (line 1)
YES'
10.0
---
kW
NO | YES
0.0…500.0
…
…
…
…
…
S4
Enable size and size for compressor group 4 (line 1)
NO
---
---
kW
---
NO | YES
0.0…500.0
Caf92
S1
Enable stages and stages for compressor group 1 (line 1)
YES'
100
---
%
NO | YES
100 | 50 | 100 | 50
75 | 100 | 25 | 50
75 | 100 | 33 | 66|100
…
…
…
…
…
S4
Enable stages and stages for compressor group 4 (line 1)
NO
---
---
kW
NO | YES
S1…S4
Caf93
C01
Size group for compressor 1 (line 1) or presence of inverter (line 1)
S1
---
S1…S4 | INV
…
…
…
…
…
C12
Size group for compressor 6 (line 1)
S1
---
S1…S4
Caf95
Min.time on
Minimum time on for Digital Scroll
TM
compressor (line 1)
60
s
0…999
Min.time off
Minimum time off for Digital Scroll
TM
compressor (line 1)
180
s
0…999
Minimum time to start
same comp.
Minimum time between startups for Digital Scroll
TM
compressor (line 1)
360
s
0…999
Reactivate startup procedure
after
Time for reactivation of startup procedure for Digital Scroll
TM
compressor (line 1)
480
min
0…9999
Cag01
Minimum voltage
Voltage corresponding to the minimum capacity of the inverter (line 1)
0.0
V
0.0…10.0
Maximum voltage
Voltage corresponding to the maximum capacity of the inverter (line 1)
10.0
V
0.0…10.0
Nominal freq.
Nominal frequency (frequency at nominal capacity) (line 1)
50
Hz
0…150
Nominal power
Nominal capacity for compressor managed by inverter at nominal frequency (line 1)
10.0
kW
0.0…500.0
Cag02
Rising time
Time to pass from minimum to maximum capacity for modulating device (line 1)
90
s
0…600
Falling time
Time to pass from maximum to minimum capacity for modulating device (line 1)
30
s
0…600
Cag03
Enable compressor modulat.
in dead zone
Enable compressor 1 modulation inside dead zone (line 1)
AB
---
Disabled
abled
Cag04
Enable suction press.backup
probe
Enable screens for the confi guration of the suction pressure backup probe (line 1)
NO
---
NO | YES
Cag05
Request in case of regulation
probe fault
Compressor forcing value in case of suction probe fault (line 1)
50.0
%
0.0…100.0
Pumpdown
Enable pumpdown function (line 1)
Disabled
---
disabled
abled
Threshold
Pumpdown end threshold (line 1)
1.5 barg
…
… (**)
Cag06
Enable anti return of liquid
Enable liquid non return function (line 1)
NO
---
NO | YES
Delay
Delay liquid non return function (line 1)
0
min
0…15
Page 110 of 172
Copyright HPL March 2021
P4114S Rev 03
Содержание Hubbard GCU2040PXB1
Страница 4: ...Page 4 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 44: ...4 Wiring Schematics Model GCU2040PXB1 Part Number D4155S Page 44 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 49: ...6 Carel PR300T CO2 Controller manual Page 49 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 144: ...Page 144 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 161: ...8 PRESSURE ENTHALPY DIAGRAM FOR R744 REFRIGERANT Page 161 of 172 Copyright HPL March 2021 P4114S Rev 03...
Страница 165: ...9 Commissioning Form Page 165 of 172 Copyright HPL March 2021 P4114S Rev 03...